← Minnesota

Tap water quality report

Fridley

EPA monitoring tested this supplier for 92 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

92
contaminants tested
11
detected
27,476
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Anoka

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2020-01-01
MR Monitoring Resolved 2020-01-01
MR Monitoring Resolved 2020-01-01
MR Monitoring Archived 1995-03-01 → 1995-03-31
MR Monitoring Archived 1995-03-01 → 1995-03-31
MR Monitoring Archived 1995-03-01 → 1995-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0095 µg/L 3/6 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
889.5 µg/L 68%
of the EPA limit 1300 µg/L
worst single sample: 1230 µg/L
90/90 SYR4 2013–2019
Lead
6.85 µg/L 46%
of the EPA limit 15 µg/L
worst single sample: 45.6 µg/L
71/90 SYR4 2013–2019
Chloroform
1.33 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
35/39 SYR4 2012–2019
Fluoride
1400 µg/L 35%
of the EPA limit 4000 µg/L
worst single sample: 1500 µg/L
33/33 SYR4 2012–2019
Bromodichloromethane
0.9000 µg/L
No EPA limit set
20/39 SYR4 2012–2019
Dichloroacetic Acid
1.77 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
14/29 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Nitrate-Nitrite
380 µg/L 3.8%
of the EPA limit 10000 µg/L
12/74 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
10.96 pCi/L 73%
of the EPA limit 15 pCi/L
worst single sample: 12 pCi/L
9/13 SYR4 2012–2019
Chromium
0.2755 µg/L 0.3%
of the EPA limit 100 µg/L
worst single sample: 0.2800 µg/L
4/8 SYR4 2013–2014
81 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzeneBenzo(A)PyreneBromoformChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDinosebEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Phone
7635723523
Email
[email protected]

Frequently asked questions about Fridley

Is Fridley tap water safe to drink?

EPA monitoring detected 11 contaminants in Fridley's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Fridley's water?

EPA monitoring detected Copper, Lead, Chloroform, Fluoride, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Fridley serve?

Fridley reports serving 27,476 people in Minnesota, per its EPA record.

Has Fridley had any water quality violations?

The EPA has 6 violations on file for Fridley, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.