Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 160 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 240 µg/L | 168/168 | SYR4 | 2012–2019 |
| Lead | 5.82 µg/L 39% of the EPA limit 15 µg/L
worst single sample: 39 µg/L | 120/168 | SYR4 | 2012–2019 |
| Fluoride | 800 µg/L 20% of the EPA limit 4000 µg/L | 104/104 | SYR4 | 2012–2019 |
| TTHM | 80.5 µg/L 101% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 108 µg/L | 86/86 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 66.8 µg/L 111% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 91 µg/L | 85/86 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 45.8 µg/L No EPA limit set
worst single sample: 59 µg/L | 83/84 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10.2 µg/L No EPA limit set
worst single sample: 12 µg/L | 77/77 | SYR4 | 2012–2019 |
| Chloroform | 71.2 µg/L No EPA limit set
worst single sample: 99 µg/L | 77/77 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 24 µg/L No EPA limit set
worst single sample: 32 µg/L | 76/84 | SYR4 | 2012–2019 |
| Lead | 0.0015 mg/L 10% of the EPA limit 0.0150 mg/L | 29/29 | LCR | 2025 |
| Nitrate | 1500 µg/L 15% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.75 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 11/77 | SYR4 | 2012–2019 |
| Barium | 32.3 µg/L 1.6% of the EPA limit 2000 µg/L
worst single sample: 33 µg/L | 8/8 | SYR4 | 2012–2019 |
| Chromium | 1.675 µg/L 1.7% of the EPA limit 100 µg/L
worst single sample: 1.7 µg/L | 6/8 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1450 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1500 µg/L | 6/6 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.38 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 2/84 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.0170 pCi/L 0.3% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2017 |
93 contaminants tested, none detected
Utility contact
Frequently asked questions about Presque Isle Utilities District
Is Presque Isle Utilities District tap water safe to drink?
EPA monitoring detected 17 contaminants in Presque Isle Utilities District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Presque Isle Utilities District's water?
EPA monitoring detected Copper, Lead, Fluoride, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Presque Isle Utilities District serve?
Presque Isle Utilities District reports serving 6,128 people in Maine, per its EPA record.
Has Presque Isle Utilities District had any water quality violations?
The EPA has 41 violations on file for Presque Isle Utilities District, of which 31 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.