← Maryland

Tap water quality report

City of Havre De Grace

EPA monitoring tested this supplier for 106 contaminants and detected 26. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

106
contaminants tested
26
detected
14,000
people served
34
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Harford

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

34
health-based violations
112
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2023-10-01 → 2023-12-31
TT Health-based Resolved 2023-10-01 → 2023-12-31
TT Health-based Resolved 2023-10-01 → 2023-12-31
TT Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
115.39 µg/L 144%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 193 µg/L
132/132 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
63.07 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 80.9 µg/L
130/131 SYR4 2012–2019
Bromodichloromethane
20.775 µg/L
No EPA limit set
worst single sample: 25.3 µg/L
56/56 SYR4 2012–2019
Chloroform
69.1 µg/L
No EPA limit set
worst single sample: 73.9 µg/L
56/56 SYR4 2012–2019
Dibromochloromethane
7.68 µg/L
No EPA limit set
worst single sample: 10.6 µg/L
55/56 SYR4 2012–2019
Dichloroacetic Acid
25.625 µg/L
No EPA limit set
worst single sample: 30.4 µg/L
46/51 SYR4 2012–2015
Trichloroacetic Acid
24.075 µg/L
No EPA limit set
worst single sample: 28 µg/L
46/51 SYR4 2012–2015
Dibromoacetic Acid
13.42 µg/L
No EPA limit set
worst single sample: 14.3 µg/L
17/51 SYR4 2012–2015
Monochloroacetic Acid
15.3 µg/L
No EPA limit set
worst single sample: 16.5 µg/L
16/51 SYR4 2012–2015
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
13/13 LCR 2025
Nitrate
2370 µg/L 24%
of the EPA limit 10000 µg/L
8/8 SYR4 2014–2018
Fluoride
752 µg/L 19%
of the EPA limit 4000 µg/L
worst single sample: 770 µg/L
7/8 SYR4 2012–2019
Barium
35 µg/L 1.8%
of the EPA limit 2000 µg/L
worst single sample: 37 µg/L
6/7 SYR4 2012–2019
Bromoform
3.76 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
5/55 SYR4 2012–2018
Di(2-ethylhexyl) Phthalate
0.9100 µg/L 15%
of the EPA limit 6 µg/L
worst single sample: 0.9500 µg/L
3/22 SYR4 2012–2019
Monobromoacetic Acid
8.67 µg/L
No EPA limit set
worst single sample: 8.9 µg/L
3/51 SYR4 2012–2015
Antimony, Total
3 µg/L 50%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Arsenic
3 µg/L 30%
of the EPA limit 10 µg/L
1/10 SYR4 2012–2019
Atrazine
0.5400 µg/L 18%
of the EPA limit 3 µg/L
1/22 SYR4 2012–2019
Beryllium, Total
0.5000 µg/L 13%
of the EPA limit 4 µg/L
1/8 SYR4 2012–2019
Cadmium
0.5000 µg/L 10%
of the EPA limit 5 µg/L
1/8 SYR4 2012–2019
Chromium
10 µg/L 10%
of the EPA limit 100 µg/L
1/8 SYR4 2012–2019
Mercury
0.2000 µg/L 10%
of the EPA limit 2 µg/L
1/8 SYR4 2012–2019
Nitrate-Nitrite
1090 µg/L 11%
of the EPA limit 10000 µg/L
1/1 SYR4 2018
Selenium
3 µg/L 6%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
Thallium, Total
1 µg/L 50%
of the EPA limit 2 µg/L
1/8 SYR4 2012–2019
80 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COLEMAN, THOMAS
Phone
410-939-1385
Email
[email protected]

Frequently asked questions about City of Havre De Grace

Is City of Havre De Grace tap water safe to drink?

EPA monitoring detected 26 contaminants in City of Havre De Grace's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Havre De Grace's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does City of Havre De Grace serve?

City of Havre De Grace reports serving 14,000 people in Maryland, per its EPA record.

Has City of Havre De Grace had any water quality violations?

The EPA has 112 violations on file for City of Havre De Grace, of which 34 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.