Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| TT | Health-based | Resolved | 2006-10-01 → 2006-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 96.648 µg/L 121% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 106.43 µg/L | 33/33 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 52.76 µg/L 88% of the EPA limit 60 µg/L
worst single sample: 71.02 µg/L | 33/33 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10.338 µg/L No EPA limit set
worst single sample: 10.85 µg/L | 25/25 | SYR4 | 2012–2019 |
| Chloroform | 90.2 µg/L No EPA limit set
worst single sample: 97.9 µg/L | 25/25 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.4 µg/L No EPA limit set
worst single sample: 35.1 µg/L | 16/16 | SYR4 | 2012–2015 |
| Nitrate | 570 µg/L 5.7% of the EPA limit 10000 µg/L | 16/22 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 33.675 µg/L No EPA limit set
worst single sample: 34.2 µg/L | 16/16 | SYR4 | 2012–2015 |
| Lead | 0.0033 mg/L 22% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Barium | 40.85 µg/L 2% of the EPA limit 2000 µg/L
worst single sample: 41.2 µg/L | 8/14 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.9675 µg/L No EPA limit set
worst single sample: 3.12 µg/L | 6/16 | SYR4 | 2012–2015 |
| Dibromochloromethane | 1.0595 µg/L No EPA limit set
worst single sample: 1.07 µg/L | 4/25 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 425 µg/L 4.3% of the EPA limit 10000 µg/L
worst single sample: 430 µg/L | 3/3 | SYR4 | 2015–2018 |
| Arsenic | 3.3 µg/L 33% of the EPA limit 10 µg/L | 1/15 | SYR4 | 2012–2019 |
| Chromium | 0.6570 µg/L 0.7% of the EPA limit 100 µg/L | 1/14 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1 pCi/L 20% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2019 |
| Dichloromethane | 2.5 µg/L 50% of the EPA limit 5 µg/L | 1/10 | SYR4 | 2012–2019 |
| Fluoride | 100 µg/L 2.5% of the EPA limit 4000 µg/L | 1/14 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.6000 pCi/L 4% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2019 |
| Selenium | 9.4 µg/L 19% of the EPA limit 50 µg/L | 1/15 | SYR4 | 2012–2019 |
| Simazine | 0.5500 µg/L 14% of the EPA limit 4 µg/L | 1/7 | SYR4 | 2012–2018 |
54 contaminants tested, none detected
Utility contact
Frequently asked questions about Town of Friendsville
Is Town of Friendsville tap water safe to drink?
EPA monitoring detected 20 contaminants in Town of Friendsville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Town of Friendsville's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Town of Friendsville serve?
Town of Friendsville reports serving 622 people in Maryland, per its EPA record.
Has Town of Friendsville had any water quality violations?
The EPA has 21 violations on file for Town of Friendsville, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.