Seekonk Water District

EPA monitoring tested this supplier for 102 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

102
contaminants tested
17
detected
13,801
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Bristol

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
14
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-08-01 → 2011-08-31
MCL Health-based Resolved 2011-08-01 → 2011-08-31
MCL Health-based Resolved 2007-07-01 → 2007-07-31
MCL Health-based Resolved 2007-07-01 → 2007-07-31
MCL Health-based Archived 1998-07-01 → 1998-07-31
MCL Health-based Archived 1998-06-01 → 1998-06-30
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MCL Health-based Resolved 1997-08-01 → 1997-08-31
TT Health-based Resolved 1996-01-01
TT Health-based Resolved 1996-01-01

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOS 0.0050 µg/L 2/2 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
69.06 µg/L 86%
of the EPA limit 80 µg/L
worst single sample: 107 µg/L
109/109 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
27.48 µg/L 46%
of the EPA limit 60 µg/L
worst single sample: 63.8 µg/L
108/108 SYR4 2012–2019
Bromodichloromethane
16.19 µg/L
No EPA limit set
worst single sample: 19.2 µg/L
98/98 SYR4 2013–2019
Chloroform
55.055 µg/L
No EPA limit set
worst single sample: 81.6 µg/L
98/98 SYR4 2013–2019
Dibromochloromethane
11 µg/L
No EPA limit set
worst single sample: 13 µg/L
97/98 SYR4 2013–2019
Trichloroacetic Acid
6.116 µg/L
No EPA limit set
worst single sample: 7.6 µg/L
97/97 SYR4 2013–2019
Dichloroacetic Acid
20 µg/L
No EPA limit set
worst single sample: 45.5 µg/L
95/97 SYR4 2013–2019
Bromoform
1.7 µg/L
No EPA limit set
worst single sample: 2.1 µg/L
79/98 SYR4 2013–2019
Dibromoacetic Acid
2.44 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
73/97 SYR4 2013–2019
Nitrate
3750 µg/L 38%
of the EPA limit 10000 µg/L
worst single sample: 4000 µg/L
58/60 SYR4 2012–2019
Monochloroacetic Acid
12.12 µg/L
No EPA limit set
worst single sample: 14.3 µg/L
28/97 SYR4 2013–2019
Lead
0.0013 mg/L 8.7%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Copper
201.25 µg/L 15%
of the EPA limit 1300 µg/L
worst single sample: 260 µg/L
6/6 SYR4 2013–2017
Monobromoacetic Acid
0.5645 µg/L
No EPA limit set
worst single sample: 0.5680 µg/L
4/97 SYR4 2013–2019
Arsenic
1 µg/L 10%
of the EPA limit 10 µg/L
1/3 SYR4 2015–2019
Fluoride
60 µg/L 1.5%
of the EPA limit 4000 µg/L
1/3 SYR4 2015–2019
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ROBERT F BERNARDO
Phone
5087618170
Email
[email protected]

Frequently asked questions about Seekonk Water District

Is Seekonk Water District tap water safe to drink?

EPA monitoring detected 17 contaminants in Seekonk Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Seekonk Water District's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Seekonk Water District serve?

Seekonk Water District reports serving 13,801 people in Massachusetts, per its EPA record.

Has Seekonk Water District had any water quality violations?

The EPA has 14 violations on file for Seekonk Water District, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.