EPA monitoring tested this supplier for 103 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

103
contaminants tested
25
detected
14,984
people served
15
health-based violations
Water source
Ground water under surface influence
Ownership
Local government
Counties served
Plymouth

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

15
health-based violations
23
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2020-01-01 → 2020-03-31
MCL Health-based Archived 2019-10-01 → 2019-12-31
MCL Health-based Archived 2019-07-01 → 2019-09-30
MCL Health-based Archived 2019-04-01 → 2019-06-30
MCL Health-based Archived 2019-01-01 → 2019-03-31
MCL Health-based Archived 2018-10-01 → 2018-12-31
MCL Health-based Archived 2018-07-01 → 2018-09-30
MCL Health-based Archived 2015-07-01 → 2015-09-30
MCL Health-based Archived 2015-04-01 → 2015-06-30
MCL Health-based Resolved 2011-09-01 → 2011-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0086 µg/L 5/6 2024
Pfpea 0.0116 µg/L 5/6 2024
PFOA 0.0089 µg/L 3/6 2024
PFBS 0.0066 µg/L 2/6 2024
PFOS 0.0114 µg/L 2/6 2024
Pfba 0.0080 µg/L 1/6 2024
Pfhpa 0.0035 µg/L 1/6 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
106.15 µg/L 133%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 168 µg/L
118/118 SYR4 2012–2019
Bromodichloromethane
36.04 µg/L
No EPA limit set
worst single sample: 49.5 µg/L
107/107 SYR4 2012–2019
Dibromochloromethane
31.67 µg/L
No EPA limit set
worst single sample: 36.8 µg/L
107/107 SYR4 2012–2019
Bromoform
13.095 µg/L
No EPA limit set
worst single sample: 14.5 µg/L
104/107 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
29 µg/L 48%
of the EPA limit 60 µg/L
worst single sample: 43 µg/L
104/117 SYR4 2012–2019
Chloroform
57.18 µg/L
No EPA limit set
worst single sample: 95.4 µg/L
102/107 SYR4 2012–2019
Trichloroacetic Acid
15.67 µg/L
No EPA limit set
worst single sample: 23.1 µg/L
82/108 SYR4 2012–2019
Dibromoacetic Acid
4.475 µg/L
No EPA limit set
worst single sample: 5.9 µg/L
66/108 SYR4 2012–2019
Dichloroacetic Acid
13.2 µg/L
No EPA limit set
worst single sample: 15.7 µg/L
53/108 SYR4 2012–2019
Nitrate
1329 µg/L 13%
of the EPA limit 10000 µg/L
worst single sample: 1340 µg/L
32/48 SYR4 2012–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
19/19 LCR 2025
Monochloroacetic Acid
5.035 µg/L
No EPA limit set
worst single sample: 5.8 µg/L
18/108 SYR4 2012–2019
Tetrachloroethylene
2.5 µg/L 50%
of the EPA limit 5 µg/L
worst single sample: 3.4 µg/L
16/97 SYR4 2012–2019
Fluoride
148 µg/L 3.7%
of the EPA limit 4000 µg/L
worst single sample: 150 µg/L
3/9 SYR4 2012–2019
Lithium
9.58 µg/L
No EPA limit set
2/6 UCMR-5 2024
Ethylbenzene
4 µg/L 0.6%
of the EPA limit 700 µg/L
1/25 SYR4 2012–2019
Monobromoacetic Acid
1.2 µg/L
No EPA limit set
1/108 SYR4 2012–2019
Xylenes, Total
19.3 µg/L 0.2%
of the EPA limit 10000 µg/L
1/25 SYR4 2012–2019
78 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ADAM N FLOOD
Phone
7818263189
Email
[email protected]

Frequently asked questions about Hanover Water Dept

Is Hanover Water Dept tap water safe to drink?

EPA monitoring detected 25 contaminants in Hanover Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hanover Water Dept's water?

EPA monitoring detected TTHM, Bromodichloromethane, Dibromochloromethane, Bromoform, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Hanover Water Dept serve?

Hanover Water Dept reports serving 14,984 people in Massachusetts, per its EPA record.

Has Hanover Water Dept had any water quality violations?

The EPA has 23 violations on file for Hanover Water Dept, of which 15 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.