Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2007-11-01 → 2007-11-30 |
| MCL | Health-based | Resolved | 2007-11-01 → 2007-11-30 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Resolved | 2007-10-01 → 2007-10-31 |
| MCL | Health-based | Archived | 2002-12-01 → 2002-12-31 |
| MCL | Health-based | Archived | 2002-12-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 1997-05-01 → 1997-05-31 |
| Other | Monitoring | Resolved | 2017-07-11 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5000 µg/L 50% of the EPA limit 10000 µg/L
worst single sample: 5800 µg/L | 136/142 | SYR4 | 2012–2019 |
| TTHM | 13.24 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 23.6 µg/L | 95/103 | SYR4 | 2012–2019 |
| Dibromochloromethane | 5.345 µg/L No EPA limit set
worst single sample: 9.1 µg/L | 92/102 | SYR4 | 2013–2019 |
| Bromoform | 2.35 µg/L No EPA limit set
worst single sample: 3.8 µg/L | 71/102 | SYR4 | 2013–2019 |
| Bromodichloromethane | 4.725 µg/L No EPA limit set
worst single sample: 8.3 µg/L | 70/102 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.35 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 61/102 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 4.62 µg/L 7.7% of the EPA limit 60 µg/L
worst single sample: 10.3 µg/L | 57/98 | SYR4 | 2012–2019 |
| Chloroform | 3.9 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 51/102 | SYR4 | 2013–2019 |
| Barium | 93.8 µg/L 4.7% of the EPA limit 2000 µg/L
worst single sample: 123 µg/L | 22/23 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 2.2 µg/L 44% of the EPA limit 5 µg/L
worst single sample: 2.8 µg/L | 21/150 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2025 |
| Dichloroacetic Acid | 2.151 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 15/102 | SYR4 | 2013–2019 |
| Arsenic | 3.55 µg/L 36% of the EPA limit 10 µg/L
worst single sample: 4 µg/L | 10/23 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 1.78 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 9/102 | SYR4 | 2013–2019 |
| Copper | 591.05 µg/L 45% of the EPA limit 1300 µg/L
worst single sample: 604 µg/L | 8/33 | SYR4 | 2014–2019 |
| Selenium | 4 µg/L 8% of the EPA limit 50 µg/L | 6/23 | SYR4 | 2012–2019 |
| Cadmium | 0.2085 µg/L 4.2% of the EPA limit 5 µg/L
worst single sample: 0.2100 µg/L | 4/23 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.06 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 4/102 | SYR4 | 2013–2019 |
| Fluoride | 80 µg/L 2% of the EPA limit 4000 µg/L | 3/30 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.9 µg/L No EPA limit set | 1/102 | SYR4 | 2013–2019 |
| Trichloroethylene | 0.6500 µg/L 13% of the EPA limit 5 µg/L | 1/78 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 2 µg/L 2.9% of the EPA limit 70 µg/L | 1/78 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Hyannis Water System, Town of Barnstable
Is Hyannis Water System, Town of Barnstable tap water safe to drink?
EPA monitoring detected 25 contaminants in Hyannis Water System, Town of Barnstable's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hyannis Water System, Town of Barnstable's water?
EPA monitoring detected Nitrate, TTHM, Dibromochloromethane, Bromoform, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Hyannis Water System, Town of Barnstable serve?
Hyannis Water System, Town of Barnstable reports serving 35,000 people in Massachusetts, per its EPA record.
Has Hyannis Water System, Town of Barnstable had any water quality violations?
The EPA has 79 violations on file for Hyannis Water System, Town of Barnstable, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.