Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2022-09-01 → 2022-09-30 |
| MCL | Health-based | Resolved | 2022-09-01 → 2022-09-30 |
| MCL | Health-based | Archived | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Archived | 1998-11-01 → 1998-11-30 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| MCL | Health-based | Archived | 1991-06-01 → 1991-06-30 |
| MR | Monitoring | Archived | 2014-10-01 → 2014-12-31 |
| MR | Monitoring | Unaddressed | 2013-01-01 |
| MR | Monitoring | Resolved | 2010-06-01 → 2010-09-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1192.5 µg/L 12% of the EPA limit 10000 µg/L
worst single sample: 2310 µg/L | 156/280 | SYR4 | 2012–2019 |
| TTHM | 86.385 µg/L 108% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 100 µg/L | 124/125 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 46.6 µg/L 78% of the EPA limit 60 µg/L
worst single sample: 80 µg/L | 99/124 | SYR4 | 2012–2019 |
| Arsenic | 44.455 µg/L 445% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 69.5 µg/L | 74/124 | SYR4 | 2012–2019 |
| Nitrite | 330.5 µg/L 33% of the EPA limit 1000 µg/L
worst single sample: 432 µg/L | 52/125 | SYR4 | 2012–2019 |
| Barium | 36 µg/L 1.8% of the EPA limit 2000 µg/L
worst single sample: 39.1 µg/L | 24/25 | SYR4 | 2012–2019 |
| Bromodichloromethane | 24.7 µg/L No EPA limit set
worst single sample: 25 µg/L | 24/25 | SYR4 | 2018–2019 |
| Chloroform | 59.7 µg/L No EPA limit set
worst single sample: 70 µg/L | 24/25 | SYR4 | 2018–2019 |
| Dibromochloromethane | 10.89 µg/L No EPA limit set
worst single sample: 12 µg/L | 24/25 | SYR4 | 2018–2019 |
| Lead | 0.0018 mg/L 12% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Dichloroacetic Acid | 21.4 µg/L No EPA limit set
worst single sample: 35 µg/L | 17/24 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 32.5 µg/L No EPA limit set
worst single sample: 40 µg/L | 16/24 | SYR4 | 2018–2019 |
| Dibromoacetic Acid | 3.52 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 13/24 | SYR4 | 2018–2019 |
| Monochloroacetic Acid | 4.25 µg/L No EPA limit set
worst single sample: 4.8 µg/L | 11/24 | SYR4 | 2018–2019 |
| Bromoform | 1.731 µg/L No EPA limit set
worst single sample: 1.92 µg/L | 10/25 | SYR4 | 2018–2019 |
| Monobromoacetic Acid | 1.1275 µg/L No EPA limit set
worst single sample: 1.14 µg/L | 6/24 | SYR4 | 2018–2019 |
| Chromium | 1.54 µg/L 1.5% of the EPA limit 100 µg/L
worst single sample: 1.6 µg/L | 4/25 | SYR4 | 2012–2019 |
| Vinyl Chloride | 0.6140 µg/L 31% of the EPA limit 2 µg/L
worst single sample: 0.6200 µg/L | 2/49 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.9130 µg/L 15% of the EPA limit 6 µg/L | 1/42 | SYR4 | 2013–2019 |
| Styrene | 0.5600 µg/L 0.6% of the EPA limit 100 µg/L | 1/49 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 0.6400 µg/L 0.9% of the EPA limit 70 µg/L | 1/49 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Wilmington Water Dept
Is Wilmington Water Dept tap water safe to drink?
EPA monitoring detected 23 contaminants in Wilmington Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wilmington Water Dept's water?
EPA monitoring detected Nitrate, TTHM, Total Haloacetic Acids (HAA5), Arsenic, Nitrite, and others. The full list with the level and data source for each is above.
How many people does Wilmington Water Dept serve?
Wilmington Water Dept reports serving 21,654 people in Massachusetts, per its EPA record.
Has Wilmington Water Dept had any water quality violations?
The EPA has 53 violations on file for Wilmington Water Dept, of which 7 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.