← Massachusetts

Tap water quality report

North Chelmsford Water Dist

EPA monitoring tested this supplier for 104 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

104
contaminants tested
20
detected
7,660
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Middlesex

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
12
violations on file
2
still open
ViolationTypeStatusPeriod
Other Monitoring Unaddressed 2025-07-02
MR Monitoring Addressed 2025-01-01
MR Monitoring Resolved 2012-04-01 → 2012-06-30
MR Monitoring Resolved 2012-04-01 → 2012-06-30
MR Monitoring Resolved 2009-01-01 → 2009-01-31
MR Monitoring Resolved 2009-01-01 → 2009-01-31
MR Monitoring Resolved 2009-01-01
MR Monitoring Resolved 2009-01-01
MR Monitoring Archived 2008-01-01 → 2008-03-31
MR Monitoring Archived 1995-05-01 → 1995-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
445 µg/L 45%
of the EPA limit 1000 µg/L
worst single sample: 650 µg/L
211/234 SYR4 2012–2019
Copper
90 µg/L 6.9%
of the EPA limit 1300 µg/L
worst single sample: 140 µg/L
27/43 SYR4 2012–2019
Bromodichloromethane
21.825 µg/L
No EPA limit set
worst single sample: 23 µg/L
24/24 SYR4 2012–2019
Chloroform
24 µg/L
No EPA limit set
worst single sample: 81.3 µg/L
24/24 SYR4 2012–2019
Dibromochloromethane
21.34 µg/L
No EPA limit set
worst single sample: 22.6 µg/L
24/24 SYR4 2012–2019
TTHM
65.16 µg/L 81%
of the EPA limit 80 µg/L
worst single sample: 93.9 µg/L
24/24 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
10.765 µg/L 18%
of the EPA limit 60 µg/L
worst single sample: 11.5 µg/L
24/24 SYR4 2012–2019
Bromoform
13.568 µg/L
No EPA limit set
worst single sample: 14.6 µg/L
23/24 SYR4 2012–2019
Lead
0.0035 mg/L 23%
of the EPA limit 0.0150 mg/L
21/21 LCR 2025
Nitrate
930 µg/L 9.3%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Trichloroacetic Acid
7.0475 µg/L
No EPA limit set
worst single sample: 8.69 µg/L
16/24 SYR4 2012–2019
Dichloroacetic Acid
4.734 µg/L
No EPA limit set
worst single sample: 5.93 µg/L
14/24 SYR4 2012–2019
Dibromoacetic Acid
3.11 µg/L
No EPA limit set
worst single sample: 3.25 µg/L
11/24 SYR4 2012–2019
Combined Uranium
17.355 µg/L 58%
of the EPA limit 30 µg/L
worst single sample: 17.7 µg/L
4/4 SYR4 2018–2019
Barium
37.85 µg/L 1.9%
of the EPA limit 2000 µg/L
worst single sample: 38 µg/L
2/2 SYR4 2012–2018
Monobromoacetic Acid
2.647 µg/L
No EPA limit set
worst single sample: 2.66 µg/L
2/24 SYR4 2012–2019
Monochloroacetic Acid
1.3655 µg/L
No EPA limit set
worst single sample: 1.38 µg/L
2/24 SYR4 2012–2019
Lithium
30.8 µg/L
No EPA limit set
2/2 UCMR-5 2024
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
1/2 SYR4 2012–2018
Fluoride
500 µg/L 13%
of the EPA limit 4000 µg/L
1/2 SYR4 2012–2018
84 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
AURORA BAS
Phone
9782513931
Email
[email protected]

Frequently asked questions about North Chelmsford Water Dist

Is North Chelmsford Water Dist tap water safe to drink?

EPA monitoring detected 20 contaminants in North Chelmsford Water Dist's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in North Chelmsford Water Dist's water?

EPA monitoring detected Chlorite, Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does North Chelmsford Water Dist serve?

North Chelmsford Water Dist reports serving 7,660 people in Massachusetts, per its EPA record.

Has North Chelmsford Water Dist had any water quality violations?

The EPA has 12 violations on file for North Chelmsford Water Dist, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.