Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Resolved | 2012-07-01 → 2012-07-31 |
| MCL | Health-based | Archived | 2011-09-01 → 2011-09-30 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Resolved | 2009-08-01 → 2009-08-31 |
| MCL | Health-based | Archived | 1999-06-01 → 1999-06-30 |
| MCL | Health-based | Archived | 1997-07-01 → 1997-07-31 |
| MCL | Health-based | Archived | 1996-08-01 → 1996-08-31 |
| MR | Monitoring | Archived | 2023-07-01 → 2023-09-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0110 µg/L | 2/8 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 22.65 µg/L No EPA limit set
worst single sample: 29 µg/L | 268/268 | SYR4 | 2012–2019 |
| TTHM | 67.595 µg/L 84% of the EPA limit 80 µg/L
worst single sample: 96.5 µg/L | 268/268 | SYR4 | 2012–2019 |
| Dibromochloromethane | 10 µg/L No EPA limit set
worst single sample: 13 µg/L | 267/268 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 39.15 µg/L 65% of the EPA limit 60 µg/L
worst single sample: 67 µg/L | 266/266 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 20 µg/L No EPA limit set
worst single sample: 33 µg/L | 265/267 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 15.51 µg/L No EPA limit set
worst single sample: 29 µg/L | 264/267 | SYR4 | 2012–2019 |
| Nitrate | 830 µg/L 8.3% of the EPA limit 10000 µg/L
worst single sample: 910 µg/L | 256/256 | SYR4 | 2012–2019 |
| Chloroform | 36.4 µg/L No EPA limit set
worst single sample: 62 µg/L | 253/268 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.1 µg/L No EPA limit set
worst single sample: 7.1 µg/L | 253/267 | SYR4 | 2012–2019 |
| Trichloroethylene | 17.3 µg/L 346% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 57 µg/L | 148/202 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 12 µg/L 17% of the EPA limit 70 µg/L
worst single sample: 16 µg/L | 147/202 | SYR4 | 2012–2019 |
| Bromoform | 2.5 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 121/268 | SYR4 | 2012–2019 |
| 1,1-Dichloroethylene | 2.4 µg/L 34% of the EPA limit 7 µg/L
worst single sample: 2.9 µg/L | 78/201 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 6.64 µg/L No EPA limit set
worst single sample: 7.4 µg/L | 65/266 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.84 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 33/267 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 26/26 | LCR | 2025 |
| Nitrite | 408 µg/L 41% of the EPA limit 1000 µg/L
worst single sample: 450 µg/L | 25/128 | SYR4 | 2012–2019 |
| Fluoride | 1300 µg/L 33% of the EPA limit 4000 µg/L
worst single sample: 1600 µg/L | 13/13 | SYR4 | 2012–2019 |
| Barium | 52.1 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 53 µg/L | 10/10 | SYR4 | 2012–2019 |
| Arsenic | 1.8 µg/L 18% of the EPA limit 10 µg/L
worst single sample: 2 µg/L | 5/10 | SYR4 | 2012–2019 |
| Selenium | 3.8 µg/L 7.6% of the EPA limit 50 µg/L
worst single sample: 4 µg/L | 5/10 | SYR4 | 2012–2019 |
| 1,1,1-Trichloroethane | 1.685 µg/L 0.8% of the EPA limit 200 µg/L
worst single sample: 1.7 µg/L | 2/202 | SYR4 | 2012–2019 |
| Cyanide | 30 µg/L 15% of the EPA limit 200 µg/L | 2/10 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 3.87 µg/L 77% of the EPA limit 5 µg/L
worst single sample: 3.9 µg/L | 2/247 | SYR4 | 2012–2019 |
| Copper | 6.2 µg/L 0.5% of the EPA limit 1300 µg/L | 1/14 | SYR4 | 2013–2019 |
77 contaminants tested, none detected
Utility contact
Frequently asked questions about Burlington Water Dept
Is Burlington Water Dept tap water safe to drink?
EPA monitoring detected 26 contaminants in Burlington Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Burlington Water Dept's water?
EPA monitoring detected Bromodichloromethane, TTHM, Dibromochloromethane, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Burlington Water Dept serve?
Burlington Water Dept reports serving 25,864 people in Massachusetts, per its EPA record.
Has Burlington Water Dept had any water quality violations?
The EPA has 261 violations on file for Burlington Water Dept, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.