| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Archived | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Archived | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Archived | 2022-10-01 → 2022-12-31 |
| MCL | Health-based | Archived | 1998-01-01 → 1998-12-31 |
| MCL | Health-based | Archived | 1997-10-01 → 1998-09-30 |
| MCL | Health-based | Archived | 1995-10-01 → 1995-10-31 |
| MCL | Health-based | Archived | 1995-07-01 → 1995-07-31 |
| MR | Monitoring | Resolved | 2014-01-01 → 2014-03-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 24.625 µg/L 41% of the EPA limit 60 µg/L
worst single sample: 33 µg/L | 116/118 | SYR4 | 2012–2019 |
| TTHM | 50.9 µg/L 64% of the EPA limit 80 µg/L
worst single sample: 80 µg/L | 112/112 | SYR4 | 2012–2019 |
| Bromodichloromethane | 18.815 µg/L No EPA limit set
worst single sample: 28 µg/L | 80/80 | SYR4 | 2012–2019 |
| Chloroform | 26 µg/L No EPA limit set
worst single sample: 28 µg/L | 80/80 | SYR4 | 2012–2019 |
| Dibromochloromethane | 18.1 µg/L No EPA limit set
worst single sample: 22 µg/L | 80/80 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 13.61 µg/L No EPA limit set
worst single sample: 22 µg/L | 74/76 | SYR4 | 2012–2019 |
| Nitrate | 710 µg/L 7.1% of the EPA limit 10000 µg/L
worst single sample: 790 µg/L | 68/68 | SYR4 | 2012–2019 |
| Bromoform | 3.98 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 67/80 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.4 µg/L No EPA limit set
worst single sample: 8.5 µg/L | 66/76 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.475 µg/L No EPA limit set
worst single sample: 7.3 µg/L | 66/76 | SYR4 | 2012–2019 |
| Bromate | 9.73 µg/L 97% of the EPA limit 10 µg/L
worst single sample: 50 µg/L | 63/75 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 6.2 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 41/76 | SYR4 | 2012–2019 |
| Nitrite | 205 µg/L 21% of the EPA limit 1000 µg/L
worst single sample: 280 µg/L | 16/33 | SYR4 | 2012–2019 |
| Lead | 0.0024 mg/L 16% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Fluoride | 1130 µg/L 28% of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.03 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 8/76 | SYR4 | 2012–2019 |
| Barium | 32.5 µg/L 1.6% of the EPA limit 2000 µg/L
worst single sample: 33 µg/L | 6/6 | SYR4 | 2012–2019 |
| Chromium | 2.26 µg/L 2.3% of the EPA limit 100 µg/L
worst single sample: 2.3 µg/L | 2/7 | SYR4 | 2012–2019 |
| Arsenic | 1.7 µg/L 17% of the EPA limit 10 µg/L | 1/7 | SYR4 | 2012–2019 |
| Cyanide | 16 µg/L 8% of the EPA limit 200 µg/L | 1/7 | SYR4 | 2012–2019 |
| Dichloromethane | 7.6 µg/L 152% of the EPA limit, at the 95th percentile of samples — 5 µg/L | 1/33 | SYR4 | 2012–2019 |
| Selenium | 1.5 µg/L 3% of the EPA limit 50 µg/L | 1/7 | SYR4 | 2012–2019 |
76 contaminants tested, none detected
Utility contact
Frequently asked questions about Billerica Water Works
Is Billerica Water Works tap water safe to drink?
EPA monitoring detected 27 contaminants in Billerica Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Billerica Water Works's water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Billerica Water Works serve?
Billerica Water Works reports serving 42,119 people in Massachusetts, per its EPA record.
Has Billerica Water Works had any water quality violations?
The EPA has 36 violations on file for Billerica Water Works, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.