Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1995-08-01 → 1995-08-31 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1992-01-01 → 1996-11-29 |
| Other | Monitoring | Resolved | 2006-01-12 |
| Other | Monitoring | Resolved | 2006-01-12 |
| Other | Monitoring | Resolved | 2005-07-12 |
| Other | Monitoring | Resolved | 2005-07-12 |
| Other | Monitoring | Resolved | 2005-07-01 |
| Other | Monitoring | Resolved | 2005-07-01 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfpea | 0.0032 µg/L | 1/4 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 51.36 µg/L 86% of the EPA limit 60 µg/L
worst single sample: 66 µg/L | 253/254 | SYR4 | 2012–2019 |
| TTHM | 77.45 µg/L 97% of the EPA limit 80 µg/L
worst single sample: 104.2 µg/L | 250/250 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 18.565 µg/L No EPA limit set
worst single sample: 23.9 µg/L | 110/110 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 24.54 µg/L No EPA limit set
worst single sample: 30 µg/L | 110/110 | SYR4 | 2015–2019 |
| Monochloroacetic Acid | 4 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 82/106 | SYR4 | 2015–2019 |
| Bromodichloromethane | 15.18 µg/L No EPA limit set
worst single sample: 17.7 µg/L | 39/39 | SYR4 | 2015–2019 |
| Chloroform | 72.27 µg/L No EPA limit set
worst single sample: 82.5 µg/L | 39/39 | SYR4 | 2015–2019 |
| Dibromochloromethane | 4.04 µg/L No EPA limit set
worst single sample: 6.8 µg/L | 39/39 | SYR4 | 2015–2019 |
| Monobromoacetic Acid | 1.92 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 25/102 | SYR4 | 2015–2018 |
| Dibromoacetic Acid | 0.7940 µg/L No EPA limit set
worst single sample: 0.8300 µg/L | 24/102 | SYR4 | 2015–2018 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2024 |
| Nitrate | 284 µg/L 2.8% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| Barium | 13.65 µg/L 0.7% of the EPA limit 2000 µg/L
worst single sample: 14 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 68.8 µg/L 1.7% of the EPA limit 4000 µg/L
worst single sample: 70 µg/L | 2/8 | SYR4 | 2012–2019 |
| Chlorobenzene | 1.9 µg/L 1.9% of the EPA limit 100 µg/L | 1/12 | SYR4 | 2012–2019 |
| Dichloromethane | 2.2 µg/L 44% of the EPA limit 5 µg/L | 1/12 | SYR4 | 2012–2019 |
| O-Dichlorobenzene | 0.6000 µg/L 0.1% of the EPA limit 600 µg/L | 1/12 | SYR4 | 2012–2019 |
| P-Dichlorobenzene | 0.7000 µg/L 0.9% of the EPA limit 75 µg/L | 1/12 | SYR4 | 2012–2019 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Worcester Dpwp, Water Supply Division
Is Worcester Dpwp, Water Supply Division tap water safe to drink?
EPA monitoring detected 19 contaminants in Worcester Dpwp, Water Supply Division's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Worcester Dpwp, Water Supply Division's water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Dichloroacetic Acid, Trichloroacetic Acid, Monochloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Worcester Dpwp, Water Supply Division serve?
Worcester Dpwp, Water Supply Division reports serving 206,518 people in Massachusetts, per its EPA record.
Has Worcester Dpwp, Water Supply Division had any water quality violations?
The EPA has 29 violations on file for Worcester Dpwp, Water Supply Division, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.