Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2004-07-01 → 2004-07-31 |
| MCL | Health-based | Resolved | 2004-07-01 → 2004-07-31 |
| MCL | Health-based | Resolved | 1998-09-01 → 1998-09-30 |
| MCL | Health-based | Resolved | 1998-09-01 → 1998-09-30 |
| MCL | Health-based | Resolved | 1996-06-01 → 1996-06-30 |
| MCL | Health-based | Resolved | 1994-09-01 → 1994-09-30 |
| MCL | Health-based | Archived | 1993-05-01 → 1993-05-31 |
| MR | Monitoring | Resolved | 2020-12-30 |
| MR | Monitoring | Resolved | 2020-12-30 |
| MR | Monitoring | Resolved | 2020-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Total Haloacetic Acids (HAA5) | 24.5 µg/L 41% of the EPA limit 60 µg/L
worst single sample: 31 µg/L | 111/111 | SYR4 | 2012–2019 |
| TTHM | 48 µg/L 60% of the EPA limit 80 µg/L
worst single sample: 84 µg/L | 110/110 | SYR4 | 2012–2019 |
| Copper | 68.2 µg/L 5.2% of the EPA limit 1300 µg/L
worst single sample: 190 µg/L | 57/57 | SYR4 | 2016 |
| Lead | 26.6 µg/L 177% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 540 µg/L | 52/57 | SYR4 | 2016 |
| Lead | 0.0033 mg/L 22% of the EPA limit 0.0150 mg/L | 34/34 | LCR | 2025 |
| Nitrate | 400 µg/L 4% of the EPA limit 10000 µg/L | 10/10 | SYR4 | 2012–2016 |
| Bromodichloromethane | 3.1865 µg/L No EPA limit set
worst single sample: 3.19 µg/L | 8/8 | SYR4 | 2018–2019 |
| Chloroform | 9.86 µg/L No EPA limit set
worst single sample: 10 µg/L | 8/8 | SYR4 | 2018–2019 |
| Dibromochloromethane | 0.9465 µg/L No EPA limit set
worst single sample: 0.9500 µg/L | 8/8 | SYR4 | 2018–2019 |
| Dichloroacetic Acid | 13.65 µg/L No EPA limit set
worst single sample: 14 µg/L | 8/8 | SYR4 | 2018–2019 |
| Monochloroacetic Acid | 4.295 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 8/8 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 1.7755 µg/L No EPA limit set
worst single sample: 1.8 µg/L | 8/8 | SYR4 | 2018–2019 |
| Barium | 36.8 µg/L 1.8% of the EPA limit 2000 µg/L
worst single sample: 39 µg/L | 5/5 | SYR4 | 2012–2016 |
| Fluoride | 1000 µg/L 25% of the EPA limit 4000 µg/L | 5/5 | SYR4 | 2012–2016 |
| Monobromoacetic Acid | 0.9095 µg/L No EPA limit set
worst single sample: 0.9200 µg/L | 2/8 | SYR4 | 2018–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Marlborough Dpw Water Div. (Mwra)
Is Marlborough Dpw Water Div. (Mwra) tap water safe to drink?
EPA monitoring detected 15 contaminants in Marlborough Dpw Water Div. (Mwra)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Marlborough Dpw Water Div. (Mwra)'s water?
EPA monitoring detected Total Haloacetic Acids (HAA5), TTHM, Copper, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does Marlborough Dpw Water Div. (Mwra) serve?
Marlborough Dpw Water Div. (Mwra) reports serving 41,799 people in Massachusetts, per its EPA record.
Has Marlborough Dpw Water Div. (Mwra) had any water quality violations?
The EPA has 37 violations on file for Marlborough Dpw Water Div. (Mwra), of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.