← Louisiana

Tap water quality report

Town of Maringouin

EPA monitoring tested this supplier for 112 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

112
contaminants tested
16
detected
3,300
people served
19
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Iberville Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

19
health-based violations
31
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2014-02-01 → 2014-02-28
MCL Health-based Resolved 2014-02-01 → 2014-02-28
MCL Health-based Resolved 2014-02-01 → 2014-02-28
MCL Health-based Resolved 2014-01-01 → 2014-01-31
MCL Health-based Resolved 2014-01-01 → 2014-01-31
MCL Health-based Resolved 2014-01-01 → 2014-01-31
MCL Health-based Archived 2013-01-01 → 2013-01-31
MCL Health-based Archived 2013-01-01 → 2013-01-31
MCL Health-based Archived 2013-01-01 → 2013-01-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
36.96 µg/L
No EPA limit set
worst single sample: 47.1 µg/L
14/14 SYR4 2013–2019
TTHM
45.925 µg/L 57%
of the EPA limit 80 µg/L
worst single sample: 58.6 µg/L
14/14 SYR4 2013–2019
Dichloroacetic Acid
17.22 µg/L
No EPA limit set
worst single sample: 18.9 µg/L
13/14 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
24.76 µg/L 41%
of the EPA limit 60 µg/L
worst single sample: 28 µg/L
13/14 SYR4 2013–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
12/12 LCR 2023
Lead
4.65 µg/L 31%
of the EPA limit 15 µg/L
worst single sample: 6 µg/L
10/24 SYR4 2013–2018
Trichloroacetic Acid
6.115 µg/L
No EPA limit set
worst single sample: 6.7 µg/L
10/14 SYR4 2013–2019
Bromodichloromethane
8.3 µg/L
No EPA limit set
worst single sample: 9.2 µg/L
7/14 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
7.01 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 7.4 µg/L
7/11 SYR4 2012–2018
Fluoride
350 µg/L 8.8%
of the EPA limit 4000 µg/L
worst single sample: 360 µg/L
6/6 SYR4 2012–2018
Monochloroacetic Acid
0.9890 µg/L
No EPA limit set
worst single sample: 1 µg/L
3/14 SYR4 2013–2019
Barium
11 µg/L 0.5%
of the EPA limit 2000 µg/L
2/6 SYR4 2012–2018
Copper
4.2185 µg/L 0.3%
of the EPA limit 1300 µg/L
worst single sample: 4.4 µg/L
2/24 SYR4 2013–2018
Dibromoacetic Acid
1.29 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/14 SYR4 2013–2019
Dibromochloromethane
2.255 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
2/14 SYR4 2013–2019
Nitrate-Nitrite
41 µg/L 0.4%
of the EPA limit 10000 µg/L
2/32 SYR4 2012–2019
96 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HARRIS, MAURICE
Phone
225-625-2630
Email
[email protected]

Frequently asked questions about Town of Maringouin

Is Town of Maringouin tap water safe to drink?

EPA monitoring detected 16 contaminants in Town of Maringouin's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Town of Maringouin's water?

EPA monitoring detected Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Lead, and others. The full list with the level and data source for each is above.

How many people does Town of Maringouin serve?

Town of Maringouin reports serving 3,300 people in Louisiana, per its EPA record.

Has Town of Maringouin had any water quality violations?

The EPA has 31 violations on file for Town of Maringouin, of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.