EPA monitoring tested this supplier for 80 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
19
detected
159
people served
6
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Calcasieu Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

6
health-based violations
27
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Archived 2003-07-01 → 2003-07-31
MCL Health-based Archived 2003-07-01 → 2003-07-31
Other Monitoring Resolved 2014-03-21
Other Monitoring Resolved 2014-03-21
MR Monitoring Resolved 2013-01-01 → 2013-08-31
MR Monitoring Resolved 2013-01-01 → 2013-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
3.145 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
12/14 SYR4 2013–2019
TTHM
13.32 µg/L 17%
of the EPA limit 80 µg/L
worst single sample: 14.2 µg/L
12/14 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
4.636 µg/L 7.7%
of the EPA limit 60 µg/L
worst single sample: 4.9 µg/L
12/14 SYR4 2013–2019
Bromodichloromethane
3.65 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
11/14 SYR4 2013–2019
Dibromoacetic Acid
1.94 µg/L
No EPA limit set
worst single sample: 1.98 µg/L
11/14 SYR4 2013–2019
Dibromochloromethane
4.6 µg/L
No EPA limit set
worst single sample: 5.5 µg/L
11/14 SYR4 2013–2019
Lead
0.00038 mg/L 2.5%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Dichloroacetic Acid
1.4655 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
8/14 SYR4 2013–2019
Lead
10.6 µg/L 71%
of the EPA limit 15 µg/L
worst single sample: 13 µg/L
7/20 SYR4 2012–2018
Trichloroacetic Acid
1.222 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
7/14 SYR4 2013–2019
Bromoform
4.125 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
6/14 SYR4 2013–2019
Fluoride
189.5 µg/L 4.7%
of the EPA limit 4000 µg/L
worst single sample: 200 µg/L
4/4 SYR4 2014–2017
Arsenic
1.98 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
2/3 SYR4 2014–2017
Copper
195 µg/L 15%
of the EPA limit 1300 µg/L
worst single sample: 200 µg/L
2/18 SYR4 2012–2018
Monobromoacetic Acid
0.3655 µg/L
No EPA limit set
worst single sample: 0.3670 µg/L
2/14 SYR4 2013–2019
Barium
160 µg/L 8%
of the EPA limit 2000 µg/L
1/3 SYR4 2014–2017
Combined Radium (-226 And -228)
0.4440 pCi/L 8.9%
of the EPA limit 5 pCi/L
1/3 SYR4 2016–2017
Di(2-ethylhexyl) Phthalate
0.5400 µg/L 9%
of the EPA limit 6 µg/L
1/3 SYR4 2016–2017
Endothall
6.3 µg/L 6.3%
of the EPA limit 100 µg/L
1/4 SYR4 2014–2017
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNitrate-NitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SIMMONS, DANIEL
Phone
985-542-7601
Email
[email protected]

Frequently asked questions about The Reserve Mhc Water

Is The Reserve Mhc Water tap water safe to drink?

EPA monitoring detected 19 contaminants in The Reserve Mhc Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in The Reserve Mhc Water's water?

EPA monitoring detected Chloroform, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.

How many people does The Reserve Mhc Water serve?

The Reserve Mhc Water reports serving 159 people in Louisiana, per its EPA record.

Has The Reserve Mhc Water had any water quality violations?

The EPA has 27 violations on file for The Reserve Mhc Water, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.