← Kentucky

Tap water quality report

Springfield Water Works

EPA monitoring tested this supplier for 98 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

98
contaminants tested
10
detected
13,205
people served
23
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Washington

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

23
health-based violations
52
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-01-01 → 2005-03-31
MCL Health-based Resolved 2005-01-01 → 2005-03-31
MCL Health-based Resolved 2005-01-01 → 2005-03-31
MCL Health-based Resolved 2005-01-01 → 2005-03-31
MCL Health-based Resolved 2005-01-01 → 2005-03-31
MCL Health-based Resolved 2005-01-01 → 2005-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
101.55 µg/L 127%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 147 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
63 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 84 µg/L
128/128 SYR4 2012–2019
Copper
888.8 µg/L 68%
of the EPA limit 1300 µg/L
worst single sample: 1870 µg/L
97/98 SYR4 2012–2019
Lead
27.4 µg/L 183%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 262 µg/L
39/89 SYR4 2013–2019
Nitrate
700 µg/L 7%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Fluoride
800 µg/L 20%
of the EPA limit 4000 µg/L
14/16 SYR4 2012–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Barium
6.65 µg/L 0.3%
of the EPA limit 2000 µg/L
worst single sample: 7 µg/L
8/8 SYR4 2012–2019
Arsenic
0.5850 µg/L 5.9%
of the EPA limit 10 µg/L
worst single sample: 0.6000 µg/L
2/8 SYR4 2012–2019
Combined Radium (-226 And -228)
2.735 pCi/L 55%
of the EPA limit 5 pCi/L
worst single sample: 2.8 pCi/L
2/2 SYR4 2014–2017
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHESSER, LINDA
Phone
859-336-5454
Email
[email protected]

Frequently asked questions about Springfield Water Works

Is Springfield Water Works tap water safe to drink?

EPA monitoring detected 10 contaminants in Springfield Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Springfield Water Works's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Lead, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Springfield Water Works serve?

Springfield Water Works reports serving 13,205 people in Kentucky, per its EPA record.

Has Springfield Water Works had any water quality violations?

The EPA has 52 violations on file for Springfield Water Works, of which 23 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.