← Kentucky

Tap water quality report

West Liberty Water Company

EPA monitoring tested this supplier for 70 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

70
contaminants tested
15
detected
2,367
people served
53
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Morgan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

53
health-based violations
70
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
84.1 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 112.2 µg/L
54/54 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
90.81 µg/L 151%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 130.8 µg/L
54/54 SYR4 2012–2019
Copper
114.25 µg/L 8.8%
of the EPA limit 1300 µg/L
worst single sample: 118 µg/L
32/38 SYR4 2012–2019
Fluoride
1210 µg/L 30%
of the EPA limit 4000 µg/L
worst single sample: 1330 µg/L
17/17 SYR4 2012–2019
Lead
1.2 µg/L 8%
of the EPA limit 15 µg/L
worst single sample: 2 µg/L
17/30 SYR4 2012–2018
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
Nitrate
300 µg/L 3%
of the EPA limit 10000 µg/L
14/16 SYR4 2012–2019
Barium
23.75 µg/L 1.2%
of the EPA limit 2000 µg/L
worst single sample: 25 µg/L
6/9 SYR4 2012–2019
Chromium
1 µg/L 1%
of the EPA limit 100 µg/L
2/9 SYR4 2012–2019
Thallium, Total
2.147 µg/L 107%
of the EPA limit, at the 95th percentile of samples — 2 µg/L
worst single sample: 2.2 µg/L
2/11 SYR4 2012–2019
Arsenic
3 µg/L 30%
of the EPA limit 10 µg/L
1/9 SYR4 2012–2019
Beryllium, Total
1 µg/L 25%
of the EPA limit 4 µg/L
1/9 SYR4 2012–2019
Cadmium
2.7 µg/L 54%
of the EPA limit 5 µg/L
1/9 SYR4 2012–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
Nitrate-Nitrite
110 µg/L 1.1%
of the EPA limit 10000 µg/L
1/1 SYR4 2014
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ADKINS, RAY
Phone
606-743-1953
Email
[email protected]

Frequently asked questions about West Liberty Water Company

Is West Liberty Water Company tap water safe to drink?

EPA monitoring detected 15 contaminants in West Liberty Water Company's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in West Liberty Water Company's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Fluoride, Lead, and others. The full list with the level and data source for each is above.

How many people does West Liberty Water Company serve?

West Liberty Water Company reports serving 2,367 people in Kentucky, per its EPA record.

Has West Liberty Water Company had any water quality violations?

The EPA has 70 violations on file for West Liberty Water Company, of which 53 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.