← Kentucky

Tap water quality report

Crittenden-Livingston Co Water District

EPA monitoring tested this supplier for 103 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

103
contaminants tested
17
detected
9,571
people served
40
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Livingston

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

40
health-based violations
313
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-10-01 → 2021-12-31
TT Health-based Resolved 2021-10-01 → 2021-12-31
TT Health-based Resolved 2021-10-01 → 2021-12-31
TT Health-based Resolved 2021-10-01 → 2021-12-31
MCL Health-based Resolved 2010-07-01 → 2010-09-30
MCL Health-based Resolved 2010-07-01 → 2010-09-30
MCL Health-based Resolved 2010-07-01 → 2010-09-30
MCL Health-based Resolved 2010-07-01 → 2010-09-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30
MCL Health-based Resolved 2010-04-01 → 2010-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0083 µg/L 1/4 2024
PFOS 0.0073 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
88.5 µg/L 6.8%
of the EPA limit 1300 µg/L
worst single sample: 540 µg/L
127/148 SYR4 2012–2019
TTHM
71.2 µg/L 89%
of the EPA limit 80 µg/L
worst single sample: 80 µg/L
57/58 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
53.6 µg/L 89%
of the EPA limit 60 µg/L
worst single sample: 74 µg/L
57/57 SYR4 2012–2019
Fluoride
1100 µg/L 28%
of the EPA limit 4000 µg/L
16/16 SYR4 2012–2019
Nitrate
750 µg/L 7.5%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Lead
24.6 µg/L 164%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 29 µg/L
9/140 SYR4 2014–2019
Barium
25.7 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 26 µg/L
7/8 SYR4 2012–2019
Atrazine
0.7720 µg/L 26%
of the EPA limit 3 µg/L
worst single sample: 0.7800 µg/L
5/24 SYR4 2012–2019
Combined Radium (-226 And -228)
0.7620 pCi/L 15%
of the EPA limit 5 pCi/L
worst single sample: 0.7800 pCi/L
2/4 SYR4 2014–2017
Nitrate-Nitrite
721 µg/L 7.2%
of the EPA limit 10000 µg/L
worst single sample: 750 µg/L
2/2 SYR4 2013–2018
Cyanide
10 µg/L 5%
of the EPA limit 200 µg/L
1/8 SYR4 2012–2019
Ethylene Dibromide
0.0300 µg/L 60%
of the EPA limit 0.0500 µg/L
1/6 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
2.35 pCi/L 16%
of the EPA limit 15 pCi/L
1/3 SYR4 2015–2017
Mercury
0.4000 µg/L 20%
of the EPA limit 2 µg/L
1/8 SYR4 2012–2019
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ADAMSON, ABBIE
Phone
270-988-2680
Email
[email protected]

Frequently asked questions about Crittenden-Livingston Co Water District

Is Crittenden-Livingston Co Water District tap water safe to drink?

EPA monitoring detected 17 contaminants in Crittenden-Livingston Co Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Crittenden-Livingston Co Water District's water?

EPA monitoring detected Copper, TTHM, Total Haloacetic Acids (HAA5), Fluoride, Nitrate, and others. The full list with the level and data source for each is above.

How many people does Crittenden-Livingston Co Water District serve?

Crittenden-Livingston Co Water District reports serving 9,571 people in Kentucky, per its EPA record.

Has Crittenden-Livingston Co Water District had any water quality violations?

The EPA has 313 violations on file for Crittenden-Livingston Co Water District, of which 40 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.