← Kentucky

Tap water quality report

Graves Co Water Dist - Sedalia

EPA monitoring tested this supplier for 72 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

72
contaminants tested
13
detected
371
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Graves

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
456
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-01-01 → 2010-12-31
MCL Health-based Resolved 2008-01-01 → 2010-12-31
MCL Health-based Resolved 2008-01-01 → 2010-12-31
MCL Health-based Resolved 2008-01-01 → 2010-12-31
Other Monitoring Resolved 2014-07-01
Other Monitoring Resolved 2014-07-01
MR Monitoring Resolved 2011-10-01 → 2011-12-31
MR Monitoring Resolved 2011-10-01 → 2011-12-31
MR Monitoring Resolved 2011-10-01 → 2011-12-31
MR Monitoring Resolved 2011-10-01 → 2011-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
6300 µg/L 63%
of the EPA limit 10000 µg/L
worst single sample: 7690 µg/L
42/42 SYR4 2012–2019
Copper
268.4 µg/L 21%
of the EPA limit 1300 µg/L
worst single sample: 282 µg/L
18/18 SYR4 2012–2019
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Fluoride
1420 µg/L 36%
of the EPA limit 4000 µg/L
worst single sample: 1700 µg/L
8/10 SYR4 2012–2019
TTHM
13.4 µg/L 17%
of the EPA limit 80 µg/L
worst single sample: 14 µg/L
4/9 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
3.17 µg/L 5.3%
of the EPA limit 60 µg/L
worst single sample: 3.3 µg/L
3/9 SYR4 2012–2019
Barium
20.8 µg/L 1%
of the EPA limit 2000 µg/L
worst single sample: 21 µg/L
2/2 SYR4 2014–2017
Lead
1.965 µg/L 13%
of the EPA limit 15 µg/L
worst single sample: 2 µg/L
2/10 SYR4 2014–2017
Atrazine
0.2800 µg/L 9.3%
of the EPA limit 3 µg/L
1/8 SYR4 2013–2019
Combined Radium (-226 And -228)
2.1 pCi/L 42%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
Gross Alpha, Excl. Radon And U
1.54 pCi/L 10%
of the EPA limit 15 pCi/L
1/1 SYR4 2014
Nitrate-Nitrite
3700 µg/L 37%
of the EPA limit 10000 µg/L
1/1 SYR4 2014
Picloram
0.3000 µg/L 0.1%
of the EPA limit 500 µg/L
1/9 SYR4 2013–2019
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHULTZ, BRENT
Phone
270-247-4661
Email
[email protected]

Frequently asked questions about Graves Co Water Dist - Sedalia

Is Graves Co Water Dist - Sedalia tap water safe to drink?

EPA monitoring detected 13 contaminants in Graves Co Water Dist - Sedalia's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Graves Co Water Dist - Sedalia's water?

EPA monitoring detected Nitrate, Copper, Lead, Fluoride, TTHM, and others. The full list with the level and data source for each is above.

How many people does Graves Co Water Dist - Sedalia serve?

Graves Co Water Dist - Sedalia reports serving 371 people in Kentucky, per its EPA record.

Has Graves Co Water Dist - Sedalia had any water quality violations?

The EPA has 456 violations on file for Graves Co Water Dist - Sedalia, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.