Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2025-10-01 → 2025-10-31 |
| TT | Health-based | Resolved | 2024-06-01 → 2024-06-30 |
| TT | Health-based | Resolved | 2024-06-01 → 2024-06-30 |
| TT | Health-based | Resolved | 2024-06-01 → 2024-06-30 |
| TT | Health-based | Resolved | 2024-06-01 → 2024-06-30 |
| TT | Health-based | Resolved | 2024-05-01 → 2024-05-31 |
| TT | Health-based | Resolved | 2024-05-01 → 2024-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 80.71 µg/L 101% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 94.5 µg/L | 159/159 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 58.85 µg/L 98% of the EPA limit 60 µg/L
worst single sample: 85.4 µg/L | 156/156 | SYR4 | 2012–2019 |
| Copper | 157.5 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 460 µg/L | 38/75 | SYR4 | 2012–2019 |
| Nitrate | 3055 µg/L 31% of the EPA limit 10000 µg/L
worst single sample: 3100 µg/L | 24/32 | SYR4 | 2012–2019 |
| Fluoride | 997 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1100 µg/L | 23/30 | SYR4 | 2012–2019 |
| Lead | 0.0050 mg/L 33% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Lead | 32.2 µg/L 215% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 73 µg/L | 13/60 | SYR4 | 2014–2017 |
| Atrazine | 0.5845 µg/L 19% of the EPA limit 3 µg/L
worst single sample: 0.5900 µg/L | 12/33 | SYR4 | 2012–2019 |
| Barium | 42.55 µg/L 2.1% of the EPA limit 2000 µg/L
worst single sample: 53 µg/L | 12/16 | SYR4 | 2012–2019 |
| Benzo(A)Pyrene | 0.0230 µg/L 11% of the EPA limit 0.2000 µg/L
worst single sample: 0.0230 µg/L | 2/31 | SYR4 | 2012–2019 |
| Cyanide | 10 µg/L 5% of the EPA limit 200 µg/L | 2/18 | SYR4 | 2012–2019 |
| Dalapon | 2.235 µg/L 1.1% of the EPA limit 200 µg/L
worst single sample: 2.3 µg/L | 2/36 | SYR4 | 2012–2019 |
| Hexachlorocyclopentadiene | 0.1300 µg/L 0.3% of the EPA limit 50 µg/L | 1/31 | SYR4 | 2012–2019 |
| Simazine | 0.0800 µg/L 2% of the EPA limit 4 µg/L | 1/32 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Edmonson Co Water District
Is Edmonson Co Water District tap water safe to drink?
EPA monitoring detected 14 contaminants in Edmonson Co Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Edmonson Co Water District's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Edmonson Co Water District serve?
Edmonson Co Water District reports serving 17,848 people in Kentucky, per its EPA record.
Has Edmonson Co Water District had any water quality violations?
The EPA has 642 violations on file for Edmonson Co Water District, of which 103 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.