Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1997-08-01 → 1997-08-31 |
| MCL | Health-based | Resolved | 1997-08-01 → 1997-08-31 |
| MCL | Health-based | Resolved | 1997-08-01 → 1997-08-31 |
| MCL | Health-based | Resolved | 1997-08-01 → 1997-08-31 |
| Other | Monitoring | Resolved | 2018-07-01 |
| Other | Monitoring | Resolved | 2018-07-01 |
| MR | Monitoring | Resolved | 2008-04-01 → 2008-06-30 |
| MR | Monitoring | Resolved | 2008-04-01 → 2008-06-30 |
| MR | Monitoring | Resolved | 2008-04-01 → 2008-06-30 |
| MR | Monitoring | Resolved | 2008-04-01 → 2008-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 248 µg/L 19% of the EPA limit 1300 µg/L
worst single sample: 499 µg/L | 145/147 | SYR4 | 2012–2019 |
| Chlorite | 793 µg/L 79% of the EPA limit 1000 µg/L
worst single sample: 940 µg/L | 115/116 | SYR4 | 2016–2019 |
| TTHM | 90.74 µg/L 113% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 109.6 µg/L | 53/53 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 46.58 µg/L 78% of the EPA limit 60 µg/L
worst single sample: 62.2 µg/L | 53/53 | SYR4 | 2012–2019 |
| Nitrate | 2400 µg/L 24% of the EPA limit 10000 µg/L
worst single sample: 2840 µg/L | 52/54 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Lead | 14 µg/L 93% of the EPA limit 15 µg/L
worst single sample: 20 µg/L | 16/140 | SYR4 | 2012–2019 |
| Fluoride | 1310 µg/L 33% of the EPA limit 4000 µg/L | 15/15 | SYR4 | 2012–2019 |
| Barium | 25.95 µg/L 1.3% of the EPA limit 2000 µg/L
worst single sample: 27 µg/L | 8/8 | SYR4 | 2012–2019 |
| Atrazine | 0.2635 µg/L 8.8% of the EPA limit 3 µg/L
worst single sample: 0.2800 µg/L | 4/8 | SYR4 | 2014–2019 |
92 contaminants tested, none detected
Utility contact
Frequently asked questions about Scottsville Water Department
Is Scottsville Water Department tap water safe to drink?
EPA monitoring detected 10 contaminants in Scottsville Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Scottsville Water Department's water?
EPA monitoring detected Copper, Chlorite, TTHM, Total Haloacetic Acids (HAA5), Nitrate, and others. The full list with the level and data source for each is above.
How many people does Scottsville Water Department serve?
Scottsville Water Department reports serving 6,864 people in Kentucky, per its EPA record.
Has Scottsville Water Department had any water quality violations?
The EPA has 395 violations on file for Scottsville Water Department, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.