Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2019-07-01 |
| Other | Monitoring | Resolved | 2019-07-01 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0058 µg/L | 1/8 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 13 µg/L No EPA limit set
worst single sample: 55 µg/L | 102/102 | SYR4 | 2013–2019 |
| Bromodichloromethane | 6.4 µg/L No EPA limit set
worst single sample: 12 µg/L | 101/102 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 8.815 µg/L No EPA limit set
worst single sample: 40 µg/L | 100/100 | SYR4 | 2013–2019 |
| TTHM | 30.4 µg/L 38% of the EPA limit 80 µg/L
worst single sample: 69 µg/L | 93/102 | SYR4 | 2013–2019 |
| Dibromochloromethane | 5.05 µg/L No EPA limit set
worst single sample: 13 µg/L | 91/102 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 20.8 µg/L 35% of the EPA limit 60 µg/L
worst single sample: 71 µg/L | 89/100 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.88 µg/L No EPA limit set
worst single sample: 5.3 µg/L | 85/100 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 9.595 µg/L No EPA limit set
worst single sample: 34 µg/L | 74/100 | SYR4 | 2013–2019 |
| Copper | 23.4 µg/L 1.8% of the EPA limit 1300 µg/L
worst single sample: 270 µg/L | 57/64 | SYR4 | 2014–2017 |
| Bromoform | 2.42 µg/L No EPA limit set
worst single sample: 9.3 µg/L | 53/102 | SYR4 | 2013–2019 |
| Nitrate | 1600 µg/L 16% of the EPA limit 10000 µg/L | 34/40 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.22 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 17/100 | SYR4 | 2013–2019 |
| Lead | 18.6 µg/L 124% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 24 µg/L | 13/64 | SYR4 | 2014–2017 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2023 |
| Monochloroacetic Acid | 12.03 µg/L No EPA limit set
worst single sample: 15 µg/L | 7/100 | SYR4 | 2013–2019 |
| Lithium | 21 µg/L No EPA limit set | 7/8 | UCMR-5 | 2025 |
| Barium | 78.95 µg/L 3.9% of the EPA limit 2000 µg/L
worst single sample: 80 µg/L | 4/4 | SYR4 | 2014–2017 |
| Chromium | 6.735 µg/L 6.7% of the EPA limit 100 µg/L
worst single sample: 7.2 µg/L | 4/4 | SYR4 | 2014–2017 |
| Selenium | 12.265 µg/L 25% of the EPA limit 50 µg/L
worst single sample: 13 µg/L | 4/4 | SYR4 | 2014–2017 |
| Arsenic | 2.09 µg/L 21% of the EPA limit 10 µg/L
worst single sample: 2.1 µg/L | 3/4 | SYR4 | 2014–2017 |
| Atrazine | 0.1900 µg/L 6.3% of the EPA limit 3 µg/L | 1/4 | SYR4 | 2014–2017 |
| Fluoride | 170 µg/L 4.3% of the EPA limit 4000 µg/L | 1/4 | SYR4 | 2014–2017 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Shawnee Co Rwd 4c
Is Shawnee Co Rwd 4c tap water safe to drink?
EPA monitoring detected 23 contaminants in Shawnee Co Rwd 4c's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Shawnee Co Rwd 4c's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Dichloroacetic Acid, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Shawnee Co Rwd 4c serve?
Shawnee Co Rwd 4c reports serving 12,000 people in Kansas, per its EPA record.
Has Shawnee Co Rwd 4c had any water quality violations?
The EPA has 2 violations on file for Shawnee Co Rwd 4c, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.