← Kansas

Tap water quality report

Andale, City of

EPA monitoring tested this supplier for 50 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
18
detected
938
people served
13
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Sedgwick

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
21
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2012-01-01 → 2012-12-31
MCL Health-based Resolved 2012-01-01 → 2012-12-31
MCL Health-based Resolved 2012-01-01 → 2012-12-31
MCL Health-based Resolved 2012-01-01 → 2012-12-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31
MCL Health-based Resolved 2008-05-01 → 2008-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1180 µg/L 91%
of the EPA limit 1300 µg/L
worst single sample: 1500 µg/L
33/33 SYR4 2012–2018
Nitrate
11230 µg/L 112%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 12000 µg/L
28/28 SYR4 2012–2019
Lead
6.1 µg/L 41%
of the EPA limit 15 µg/L
worst single sample: 8.1 µg/L
24/33 SYR4 2012–2018
Lead
0.0093 mg/L 62%
of the EPA limit 0.0150 mg/L
8/8 LCR 2024
Bromodichloromethane
2.02 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
7/7 SYR4 2012–2019
Bromoform
4.29 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
7/7 SYR4 2012–2019
Dibromoacetic Acid
2.2 µg/L
No EPA limit set
7/7 SYR4 2012–2019
Dibromochloromethane
4.46 µg/L
No EPA limit set
worst single sample: 4.7 µg/L
7/7 SYR4 2012–2019
TTHM
10.7 µg/L 13%
of the EPA limit 80 µg/L
worst single sample: 11 µg/L
7/7 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
2.725 µg/L 4.5%
of the EPA limit 60 µg/L
worst single sample: 2.8 µg/L
4/7 SYR4 2012–2019
Arsenic
1.78 µg/L 18%
of the EPA limit 10 µg/L
worst single sample: 1.8 µg/L
3/3 SYR4 2012–2018
Barium
205.2 µg/L 10%
of the EPA limit 2000 µg/L
worst single sample: 208 µg/L
3/3 SYR4 2012–2018
Chromium
5.26 µg/L 5.3%
of the EPA limit 100 µg/L
worst single sample: 5.4 µg/L
3/3 SYR4 2012–2018
Selenium
5.39 µg/L 11%
of the EPA limit 50 µg/L
worst single sample: 5.5 µg/L
3/3 SYR4 2012–2018
Fluoride
269 µg/L 6.7%
of the EPA limit 4000 µg/L
worst single sample: 270 µg/L
2/3 SYR4 2012–2018
Monobromoacetic Acid
0.6685 µg/L
No EPA limit set
worst single sample: 0.6700 µg/L
2/7 SYR4 2012–2019
Combined Radium (-226 And -228)
0.9000 pCi/L 18%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
Dichloroacetic Acid
0.5000 µg/L
No EPA limit set
1/7 SYR4 2012–2019
32 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAtrazineBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideChloroformDichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HEIN, PATTY
Phone
316-444-2351
Email
[email protected]

Frequently asked questions about Andale, City of

Is Andale, City of tap water safe to drink?

EPA monitoring detected 18 contaminants in Andale, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Andale, City of's water?

EPA monitoring detected Copper, Nitrate, Lead, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Andale, City of serve?

Andale, City of reports serving 938 people in Kansas, per its EPA record.

Has Andale, City of had any water quality violations?

The EPA has 21 violations on file for Andale, City of, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.