← Kansas

Tap water quality report

Reno Co Rwd 3

EPA monitoring tested this supplier for 50 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
20
detected
450
people served
25
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Reno

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

25
health-based violations
34
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2023-07-01 → 2023-07-31
MCL Health-based Resolved 2023-07-01 → 2023-07-31
MCL Health-based Resolved 2023-07-01 → 2023-07-31
MCL Health-based Resolved 2023-07-01 → 2023-07-31
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2011-01-01 → 2011-12-31
MCL Health-based Resolved 2011-01-01 → 2011-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
9600 µg/L 96%
of the EPA limit 10000 µg/L
worst single sample: 11000 µg/L
58/58 SYR4 2012–2019
Copper
130 µg/L 10%
of the EPA limit 1300 µg/L
worst single sample: 150 µg/L
22/22 SYR4 2012–2018
Lead
4.25 µg/L 28%
of the EPA limit 15 µg/L
worst single sample: 4.7 µg/L
10/22 SYR4 2012–2018
Lead
0.0016 mg/L 11%
of the EPA limit 0.0150 mg/L
8/8 LCR 2024
Arsenic
1.7 µg/L 17%
of the EPA limit 10 µg/L
6/6 SYR4 2012–2018
Barium
150 µg/L 7.5%
of the EPA limit 2000 µg/L
6/6 SYR4 2012–2018
Fluoride
367.5 µg/L 9.2%
of the EPA limit 4000 µg/L
worst single sample: 370 µg/L
6/6 SYR4 2012–2018
Selenium
1.975 µg/L 4%
of the EPA limit 50 µg/L
worst single sample: 2 µg/L
6/6 SYR4 2012–2018
Bromodichloromethane
8.88 µg/L
No EPA limit set
worst single sample: 8.9 µg/L
5/5 SYR4 2012–2019
Bromoform
3.86 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
5/5 SYR4 2012–2019
Chloroform
7.86 µg/L
No EPA limit set
worst single sample: 7.9 µg/L
5/5 SYR4 2012–2019
Dibromoacetic Acid
3.78 µg/L
No EPA limit set
worst single sample: 4 µg/L
5/5 SYR4 2012–2019
Dibromochloromethane
9.3 µg/L
No EPA limit set
worst single sample: 9.4 µg/L
5/5 SYR4 2012–2019
Dichloroacetic Acid
3.96 µg/L
No EPA limit set
worst single sample: 4.2 µg/L
5/5 SYR4 2012–2019
TTHM
29 µg/L 36%
of the EPA limit 80 µg/L
5/5 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
9.32 µg/L 16%
of the EPA limit 60 µg/L
worst single sample: 9.6 µg/L
5/5 SYR4 2012–2019
Trichloroacetic Acid
1.9 µg/L
No EPA limit set
5/5 SYR4 2012–2019
Chromium
4.125 µg/L 4.1%
of the EPA limit 100 µg/L
worst single sample: 4.2 µg/L
4/6 SYR4 2012–2018
Monobromoacetic Acid
1.19 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
3/5 SYR4 2012–2019
Atrazine
0.1600 µg/L 5.3%
of the EPA limit 3 µg/L
1/6 SYR4 2012–2018
30 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideCombined Radium (-226 And -228)DichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ECKHOFF, SARA
Phone
620-960-0570
Email
[email protected]

Frequently asked questions about Reno Co Rwd 3

Is Reno Co Rwd 3 tap water safe to drink?

EPA monitoring detected 20 contaminants in Reno Co Rwd 3's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Reno Co Rwd 3's water?

EPA monitoring detected Nitrate, Copper, Lead, Lead, Arsenic, and others. The full list with the level and data source for each is above.

How many people does Reno Co Rwd 3 serve?

Reno Co Rwd 3 reports serving 450 people in Kansas, per its EPA record.

Has Reno Co Rwd 3 had any water quality violations?

The EPA has 34 violations on file for Reno Co Rwd 3, of which 25 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.