← Kansas

Tap water quality report

Ottawa Co Rwd 2

EPA monitoring tested this supplier for 50 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
21
detected
1,794
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Ottawa

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
23
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 1987-03-03 → 1987-06-02
MCL Health-based Resolved 1987-03-03 → 1987-06-02
MCL Health-based Resolved 1987-03-03 → 1987-06-02
MCL Health-based Resolved 1987-03-03 → 1987-06-02
MON Monitoring Resolved 2024-02-01 → 2024-02-29
MON Monitoring Resolved 2024-02-01 → 2024-02-29
MON Monitoring Resolved 2024-02-01 → 2024-02-29
MON Monitoring Resolved 2024-02-01 → 2024-02-29
MR Monitoring Resolved 2024-01-01 → 2024-03-31
MR Monitoring Resolved 2024-01-01 → 2024-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1300 µg/L 100%
of the EPA limit 1300 µg/L
worst single sample: 1800 µg/L
86/86 SYR4 2014–2019
Nitrate
2000 µg/L 20%
of the EPA limit 10000 µg/L
worst single sample: 2100 µg/L
42/42 SYR4 2012–2019
Lead
0.0033 mg/L 22%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Lead
4.035 µg/L 27%
of the EPA limit 15 µg/L
worst single sample: 4.2 µg/L
12/86 SYR4 2014–2019
Bromodichloromethane
2.85 µg/L
No EPA limit set
worst single sample: 3 µg/L
7/7 SYR4 2012–2019
Bromoform
4.15 µg/L
No EPA limit set
worst single sample: 4.9 µg/L
7/7 SYR4 2012–2019
Dibromoacetic Acid
1.87 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
7/7 SYR4 2012–2019
Dibromochloromethane
4 µg/L
No EPA limit set
worst single sample: 4.3 µg/L
7/7 SYR4 2012–2019
TTHM
12.8 µg/L 16%
of the EPA limit 80 µg/L
worst single sample: 14 µg/L
7/7 SYR4 2012–2019
Chloroform
7.48 µg/L
No EPA limit set
worst single sample: 9 µg/L
5/7 SYR4 2012–2019
Dichloroacetic Acid
8.148 µg/L
No EPA limit set
worst single sample: 10 µg/L
5/7 SYR4 2012–2019
Barium
124.75 µg/L 6.2%
of the EPA limit 2000 µg/L
worst single sample: 130 µg/L
4/4 SYR4 2014–2017
Fluoride
274 µg/L 6.9%
of the EPA limit 4000 µg/L
worst single sample: 280 µg/L
3/4 SYR4 2014–2017
Atrazine
0.2935 µg/L 9.8%
of the EPA limit 3 µg/L
worst single sample: 0.3000 µg/L
2/5 SYR4 2013–2019
Chromium
1.1 µg/L 1.1%
of the EPA limit 100 µg/L
2/4 SYR4 2014–2017
Selenium
3.255 µg/L 6.5%
of the EPA limit 50 µg/L
worst single sample: 3.3 µg/L
2/4 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
18.175 µg/L 30%
of the EPA limit 60 µg/L
worst single sample: 19 µg/L
2/7 SYR4 2012–2019
Combined Radium (-226 And -228)
2.2 pCi/L 44%
of the EPA limit 5 pCi/L
1/2 SYR4 2015–2016
Monobromoacetic Acid
0.5600 µg/L
No EPA limit set
1/7 SYR4 2012–2019
Trichloroacetic Acid
8.1 µg/L
No EPA limit set
1/7 SYR4 2012–2019
Trichloroethylene
0.5800 µg/L 12%
of the EPA limit 5 µg/L
1/6 SYR4 2013–2019
29 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalArsenicBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GRIFFIN, NORMA
Phone
785-823-8605
Email
[email protected]

Frequently asked questions about Ottawa Co Rwd 2

Is Ottawa Co Rwd 2 tap water safe to drink?

EPA monitoring detected 21 contaminants in Ottawa Co Rwd 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ottawa Co Rwd 2's water?

EPA monitoring detected Copper, Nitrate, Lead, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Ottawa Co Rwd 2 serve?

Ottawa Co Rwd 2 reports serving 1,794 people in Kansas, per its EPA record.

Has Ottawa Co Rwd 2 had any water quality violations?

The EPA has 23 violations on file for Ottawa Co Rwd 2, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.