Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1986-06-09 → 1987-06-08 |
| MCL | Health-based | Resolved | 1986-06-09 → 1987-06-08 |
| MCL | Health-based | Archived | 1985-01-21 → 1986-01-20 |
| MCL | Health-based | Archived | 1984-01-09 → 1985-01-08 |
| MCL | Health-based | Archived | 1982-10-01 → 1983-09-30 |
| MCL | Health-based | Archived | 1982-03-08 → 1983-03-07 |
| MCL | Health-based | Archived | 1980-11-10 → 1981-11-09 |
| MCL | Health-based | Archived | 1980-02-13 → 1981-02-12 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 8300 µg/L 83% of the EPA limit 10000 µg/L
worst single sample: 8400 µg/L | 90/90 | SYR4 | 2012–2019 |
| Fluoride | 3800 µg/L 95% of the EPA limit 4000 µg/L
worst single sample: 3900 µg/L | 41/41 | SYR4 | 2012–2019 |
| Copper | 537 µg/L 41% of the EPA limit 1300 µg/L
worst single sample: 740 µg/L | 38/39 | SYR4 | 2013–2019 |
| Arsenic | 8.62 µg/L 86% of the EPA limit 10 µg/L
worst single sample: 8.7 µg/L | 9/9 | SYR4 | 2013–2019 |
| Barium | 100 µg/L 5% of the EPA limit 2000 µg/L | 9/9 | SYR4 | 2013–2019 |
| Selenium | 20.2 µg/L 40% of the EPA limit 50 µg/L
worst single sample: 21 µg/L | 9/9 | SYR4 | 2013–2019 |
| Lead | 0.0044 mg/L 29% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2025 |
| Bromodichloromethane | 5.25 µg/L No EPA limit set
worst single sample: 5.5 µg/L | 6/6 | SYR4 | 2014–2019 |
| Bromoform | 17 µg/L No EPA limit set | 6/6 | SYR4 | 2014–2019 |
| Chromium | 3.6 µg/L 3.6% of the EPA limit 100 µg/L
worst single sample: 3.7 µg/L | 6/9 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 8.175 µg/L No EPA limit set
worst single sample: 8.8 µg/L | 6/6 | SYR4 | 2014–2019 |
| Dibromochloromethane | 12.5 µg/L No EPA limit set
worst single sample: 13 µg/L | 6/6 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 2.025 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 6/6 | SYR4 | 2014–2019 |
| TTHM | 36.25 µg/L 45% of the EPA limit 80 µg/L
worst single sample: 37 µg/L | 6/6 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 11 µg/L 18% of the EPA limit 60 µg/L | 6/6 | SYR4 | 2014–2019 |
| Chloroform | 1.236 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 5/6 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 1.26 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 5/6 | SYR4 | 2014–2019 |
| Lead | 2.52 µg/L 17% of the EPA limit 15 µg/L
worst single sample: 2.7 µg/L | 5/39 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.8950 pCi/L 18% of the EPA limit 5 pCi/L
worst single sample: 0.9000 pCi/L | 2/6 | SYR4 | 2012–2019 |
| Combined Uranium | 12 µg/L 40% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2012 |
| Ethylene Dibromide | 0.0300 µg/L 60% of the EPA limit 0.0500 µg/L | 1/14 | SYR4 | 2012–2018 |
| Gross Alpha, Excl. Radon And U | 7.9 pCi/L 53% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2012 |
| Monochloroacetic Acid | 2.8 µg/L No EPA limit set | 1/6 | SYR4 | 2014–2019 |
29 contaminants tested, none detected
Utility contact
Frequently asked questions about Dighton, City of
Is Dighton, City of tap water safe to drink?
EPA monitoring detected 23 contaminants in Dighton, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Dighton, City of's water?
EPA monitoring detected Nitrate, Fluoride, Copper, Arsenic, Barium, and others. The full list with the level and data source for each is above.
How many people does Dighton, City of serve?
Dighton, City of reports serving 954 people in Kansas, per its EPA record.
Has Dighton, City of had any water quality violations?
The EPA has 132 violations on file for Dighton, City of, of which 8 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.