Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2003-04-19 |
| TT | Health-based | Resolved | 2003-04-19 |
| TT | Health-based | Resolved | 2003-04-19 |
| TT | Health-based | Resolved | 2003-04-19 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
| RPT | Monitoring | Unaddressed | 2025-07-02 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
| RPT | Monitoring | Resolved | 2024-10-17 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1300 µg/L 100% of the EPA limit 1300 µg/L
worst single sample: 1400 µg/L | 22/22 | SYR4 | 2014–2017 |
| Nitrate | 2000 µg/L 20% of the EPA limit 10000 µg/L | 20/20 | SYR4 | 2012–2019 |
| Lead | 13.84 µg/L 92% of the EPA limit 15 µg/L
worst single sample: 27 µg/L | 15/22 | SYR4 | 2014–2017 |
| Lead | 0.0039 mg/L 26% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2023 |
| Bromodichloromethane | 4.725 µg/L No EPA limit set
worst single sample: 4.9 µg/L | 6/6 | SYR4 | 2014–2019 |
| Bromoform | 2.6 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 6/6 | SYR4 | 2014–2019 |
| Chloroform | 1.95 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 6/6 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 3 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 6/6 | SYR4 | 2014–2019 |
| Dibromochloromethane | 5.775 µg/L No EPA limit set
worst single sample: 6 µg/L | 6/6 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 1.3 µg/L No EPA limit set | 6/6 | SYR4 | 2014–2019 |
| TTHM | 14 µg/L 18% of the EPA limit 80 µg/L | 6/6 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 5.4 µg/L 9% of the EPA limit 60 µg/L
worst single sample: 5.7 µg/L | 6/6 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 0.6310 µg/L No EPA limit set
worst single sample: 0.6400 µg/L | 3/6 | SYR4 | 2014–2019 |
| Arsenic | 1.58 µg/L 16% of the EPA limit 10 µg/L
worst single sample: 1.6 µg/L | 2/2 | SYR4 | 2015–2017 |
| Barium | 209 µg/L 10% of the EPA limit 2000 µg/L
worst single sample: 210 µg/L | 2/2 | SYR4 | 2015–2017 |
| Monobromoacetic Acid | 1.1705 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 2/6 | SYR4 | 2014–2019 |
| Selenium | 3.99 µg/L 8% of the EPA limit 50 µg/L
worst single sample: 4 µg/L | 2/2 | SYR4 | 2015–2017 |
| Lithium | 18 µg/L No EPA limit set | 2/2 | UCMR-5 | 2023 |
| Chromium | 1.5 µg/L 1.5% of the EPA limit 100 µg/L | 1/2 | SYR4 | 2015–2017 |
| Combined Radium (-226 And -228) | 1 pCi/L 20% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Fluoride | 170 µg/L 4.3% of the EPA limit 4000 µg/L | 1/2 | SYR4 | 2015–2017 |
| Xylenes, Total | 1.1 µg/L 0% of the EPA limit 10000 µg/L | 1/3 | SYR4 | 2012–2018 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Perry, City of
Is Perry, City of tap water safe to drink?
EPA monitoring detected 22 contaminants in Perry, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Perry, City of's water?
EPA monitoring detected Copper, Nitrate, Lead, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Perry, City of serve?
Perry, City of reports serving 858 people in Kansas, per its EPA record.
Has Perry, City of had any water quality violations?
The EPA has 23 violations on file for Perry, City of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.