Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Unaddressed | 2026-01-01 |
| MR | Monitoring | Unaddressed | 2026-01-01 |
| MR | Monitoring | Unaddressed | 2024-07-01 |
| MR | Monitoring | Unaddressed | 2024-07-01 |
| MR | Monitoring | Unaddressed | 2024-07-01 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MR | Monitoring | Resolved | 2022-10-01 → 2022-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 745.5 µg/L 57% of the EPA limit 1300 µg/L
worst single sample: 1100 µg/L | 22/22 | SYR4 | 2014–2017 |
| Nitrate | 1700 µg/L 17% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Lead | 0.0017 mg/L 11% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Lead | 23.12 µg/L 154% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 37 µg/L | 9/22 | SYR4 | 2014–2017 |
| Dibromoacetic Acid | 3.46 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 5/5 | SYR4 | 2014–2019 |
| Dibromochloromethane | 9.62 µg/L No EPA limit set
worst single sample: 11 µg/L | 5/5 | SYR4 | 2014–2019 |
| Bromodichloromethane | 20.63 µg/L No EPA limit set
worst single sample: 23 µg/L | 4/5 | SYR4 | 2014–2019 |
| Chloroform | 70.21 µg/L No EPA limit set
worst single sample: 82 µg/L | 4/5 | SYR4 | 2014–2019 |
| TTHM | 97.4 µg/L 122% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 110 µg/L | 4/5 | SYR4 | 2014–2019 |
| Bromoform | 4.57 µg/L No EPA limit set
worst single sample: 4.6 µg/L | 3/5 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 108.69 µg/L 181% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 120 µg/L | 3/5 | SYR4 | 2014–2019 |
| Barium | 99.95 µg/L 5% of the EPA limit 2000 µg/L
worst single sample: 100 µg/L | 2/2 | SYR4 | 2014–2017 |
| Chromium | 2.38 µg/L 2.4% of the EPA limit 100 µg/L
worst single sample: 2.4 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dichloroacetic Acid | 41.91 µg/L No EPA limit set
worst single sample: 44 µg/L | 2/5 | SYR4 | 2014–2019 |
| Selenium | 2.59 µg/L 5.2% of the EPA limit 50 µg/L
worst single sample: 2.6 µg/L | 2/2 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 61.805 µg/L No EPA limit set
worst single sample: 65 µg/L | 2/5 | SYR4 | 2014–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2014–2017 |
| Atrazine | 0.5200 µg/L 17% of the EPA limit 3 µg/L | 1/4 | SYR4 | 2012–2018 |
| Fluoride | 180 µg/L 4.5% of the EPA limit 4000 µg/L | 1/2 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 1.4 µg/L No EPA limit set | 1/5 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 4.1 µg/L No EPA limit set | 1/5 | SYR4 | 2014–2019 |
41 contaminants tested, none detected
Utility contact
Frequently asked questions about Ozawkie, City of
Is Ozawkie, City of tap water safe to drink?
EPA monitoring detected 21 contaminants in Ozawkie, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ozawkie, City of's water?
EPA monitoring detected Copper, Nitrate, Lead, Lead, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Ozawkie, City of serve?
Ozawkie, City of reports serving 636 people in Kansas, per its EPA record.
Has Ozawkie, City of had any water quality violations?
The EPA has 30 violations on file for Ozawkie, City of, of which 0 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.