← Kansas

Tap water quality report

Brookover Land Enterprises, L.P.

EPA monitoring tested this supplier for 50 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
18
detected
1,180
people served
16
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Finney

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

16
health-based violations
22
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2010-10-01 → 2010-10-31
MCL Health-based Resolved 2006-07-01 → 2006-07-31
MCL Health-based Resolved 2006-07-01 → 2006-07-31
MCL Health-based Resolved 2006-07-01 → 2006-07-31
MCL Health-based Resolved 2006-07-01 → 2006-07-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
11000 µg/L 110%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 12000 µg/L
56/56 SYR4 2012–2019
Copper
220 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 670 µg/L
37/38 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
11/11 LCR 2023
Bromoform
5.53 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
7/7 SYR4 2013–2019
Dibromoacetic Acid
4.41 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
7/7 SYR4 2013–2019
TTHM
7.28 µg/L 9.1%
of the EPA limit 80 µg/L
worst single sample: 7.7 µg/L
7/7 SYR4 2013–2019
Barium
46.75 µg/L 2.3%
of the EPA limit 2000 µg/L
worst single sample: 51 µg/L
6/6 SYR4 2013–2019
Dibromochloromethane
1.875 µg/L
No EPA limit set
worst single sample: 2 µg/L
6/7 SYR4 2013–2019
Lead
32 µg/L 213%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 33 µg/L
6/38 SYR4 2013–2019
Selenium
13 µg/L 26%
of the EPA limit 50 µg/L
6/6 SYR4 2013–2019
Fluoride
324 µg/L 8.1%
of the EPA limit 4000 µg/L
worst single sample: 340 µg/L
5/6 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
7.46 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 7.9 µg/L
5/7 SYR4 2013–2019
Arsenic
2.695 µg/L 27%
of the EPA limit 10 µg/L
worst single sample: 2.8 µg/L
4/6 SYR4 2013–2019
Monobromoacetic Acid
0.9170 µg/L
No EPA limit set
worst single sample: 0.9600 µg/L
3/7 SYR4 2013–2019
Dichloroacetic Acid
2.075 µg/L
No EPA limit set
worst single sample: 2.1 µg/L
2/7 SYR4 2013–2019
Chromium
2.1 µg/L 2.1%
of the EPA limit 100 µg/L
1/6 SYR4 2013–2019
Combined Radium (-226 And -228)
2.5 pCi/L 50%
of the EPA limit 5 pCi/L
1/3 SYR4 2014–2017
Monochloroacetic Acid
2.8 µg/L
No EPA limit set
1/7 SYR4 2013–2019
32 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAtrazineBenzeneBeryllium, TotalBromodichloromethaneChlorobenzeneCadmiumCarbon TetrachlorideChloroformDichloromethaneEthylene DibromideEthylbenzeneMercuryStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BROOKOVER, TY
Phone
620-275-9206
Email
[email protected]

Frequently asked questions about Brookover Land Enterprises, L.P.

Is Brookover Land Enterprises, L.P. tap water safe to drink?

EPA monitoring detected 18 contaminants in Brookover Land Enterprises, L.P.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Brookover Land Enterprises, L.P.'s water?

EPA monitoring detected Nitrate, Copper, Lead, Bromoform, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Brookover Land Enterprises, L.P. serve?

Brookover Land Enterprises, L.P. reports serving 1,180 people in Kansas, per its EPA record.

Has Brookover Land Enterprises, L.P. had any water quality violations?

The EPA has 22 violations on file for Brookover Land Enterprises, L.P., of which 16 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.