← Kansas

Tap water quality report

Ellis Co Rwd 6

EPA monitoring tested this supplier for 50 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
20
detected
383
people served
5
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Ellis

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
208
violations on file
9
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2015-09-30
TT Health-based Resolved 2015-09-30
TT Health-based Resolved 2015-09-30
TT Health-based Resolved 2015-09-30
TT Health-based Resolved 2015-09-30
MR Monitoring Unaddressed 2026-01-01
Other Monitoring Unaddressed 2023-10-02
Other Monitoring Unaddressed 2023-10-02
Other Monitoring Unaddressed 2023-07-01
Other Monitoring Unaddressed 2022-11-06

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4900 µg/L 49%
of the EPA limit 10000 µg/L
worst single sample: 5000 µg/L
42/42 SYR4 2012–2019
Copper
206 µg/L 16%
of the EPA limit 1300 µg/L
worst single sample: 240 µg/L
25/25 SYR4 2012–2018
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Lead
3.125 µg/L 21%
of the EPA limit 15 µg/L
worst single sample: 3.2 µg/L
6/25 SYR4 2012–2018
Arsenic
6.4 µg/L 64%
of the EPA limit 10 µg/L
worst single sample: 6.7 µg/L
4/4 SYR4 2012–2018
Barium
308.5 µg/L 15%
of the EPA limit 2000 µg/L
worst single sample: 310 µg/L
4/4 SYR4 2012–2018
Fluoride
314 µg/L 7.9%
of the EPA limit 4000 µg/L
worst single sample: 320 µg/L
4/4 SYR4 2012–2018
Selenium
8.905 µg/L 18%
of the EPA limit 50 µg/L
worst single sample: 9.4 µg/L
4/4 SYR4 2012–2018
Chromium
3.76 µg/L 3.8%
of the EPA limit 100 µg/L
worst single sample: 3.8 µg/L
3/4 SYR4 2012–2018
Bromodichloromethane
7.515 µg/L
No EPA limit set
worst single sample: 7.7 µg/L
2/2 SYR4 2014–2018
Bromoform
6.01 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
2/2 SYR4 2014–2018
Chloroform
2.255 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
2/2 SYR4 2014–2018
Dibromoacetic Acid
4.415 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
2/2 SYR4 2014–2018
Dibromochloromethane
10.795 µg/L
No EPA limit set
worst single sample: 11 µg/L
2/2 SYR4 2014–2018
Dichloroacetic Acid
1.49 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
2/2 SYR4 2014–2018
Monobromoacetic Acid
0.5785 µg/L
No EPA limit set
worst single sample: 0.5800 µg/L
2/2 SYR4 2014–2018
TTHM
26.5 µg/L 33%
of the EPA limit 80 µg/L
worst single sample: 27 µg/L
2/2 SYR4 2014–2018
Total Haloacetic Acids (HAA5)
6.505 µg/L 11%
of the EPA limit 60 µg/L
worst single sample: 6.6 µg/L
2/2 SYR4 2014–2018
Atrazine
0.0280 µg/L 0.9%
of the EPA limit 3 µg/L
1/4 SYR4 2013–2019
Combined Radium (-226 And -228)
0.9000 pCi/L 18%
of the EPA limit 5 pCi/L
1/1 SYR4 2017
30 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WALTERS JR, TOM
Phone
785-623-6767
Email
[email protected]

Frequently asked questions about Ellis Co Rwd 6

Is Ellis Co Rwd 6 tap water safe to drink?

EPA monitoring detected 20 contaminants in Ellis Co Rwd 6's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ellis Co Rwd 6's water?

EPA monitoring detected Nitrate, Copper, Lead, Lead, Arsenic, and others. The full list with the level and data source for each is above.

How many people does Ellis Co Rwd 6 serve?

Ellis Co Rwd 6 reports serving 383 people in Kansas, per its EPA record.

Has Ellis Co Rwd 6 had any water quality violations?

The EPA has 208 violations on file for Ellis Co Rwd 6, of which 5 are health-based (a contaminant limit or required treatment was breached) and 9 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.