← Kansas

Tap water quality report

Wakefield, City of

EPA monitoring tested this supplier for 50 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

50
contaminants tested
20
detected
846
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Clay

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
51
violations on file
2
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2002-10-01 → 2002-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Resolved 2000-10-01 → 2000-12-31
MCL Health-based Archived 1988-09-19 → 1988-12-18
MCL Health-based Archived 1988-09-19 → 1988-12-18

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
788 µg/L 61%
of the EPA limit 1300 µg/L
worst single sample: 1000 µg/L
22/22 SYR4 2014–2017
Nitrate
4500 µg/L 45%
of the EPA limit 10000 µg/L
20/20 SYR4 2012–2019
Lead
7.325 µg/L 49%
of the EPA limit 15 µg/L
worst single sample: 12 µg/L
18/22 SYR4 2014–2017
Lead
0.0048 mg/L 32%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Bromodichloromethane
9.45 µg/L
No EPA limit set
worst single sample: 10 µg/L
6/6 SYR4 2012–2019
Bromoform
5.8 µg/L
No EPA limit set
worst single sample: 6.4 µg/L
6/6 SYR4 2012–2019
Chloroform
4.9 µg/L
No EPA limit set
6/6 SYR4 2012–2019
Dibromoacetic Acid
3.425 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
6/6 SYR4 2012–2019
Dibromochloromethane
11.675 µg/L
No EPA limit set
worst single sample: 13 µg/L
6/6 SYR4 2012–2019
Dichloroacetic Acid
1.875 µg/L
No EPA limit set
worst single sample: 2 µg/L
6/6 SYR4 2012–2019
TTHM
31.5 µg/L 39%
of the EPA limit 80 µg/L
worst single sample: 34 µg/L
6/6 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
6.76 µg/L 11%
of the EPA limit 60 µg/L
worst single sample: 7.1 µg/L
5/6 SYR4 2012–2019
Monobromoacetic Acid
1.68 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
3/6 SYR4 2012–2019
Arsenic
1.985 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
2/2 SYR4 2014–2017
Barium
379 µg/L 19%
of the EPA limit 2000 µg/L
worst single sample: 380 µg/L
2/2 SYR4 2014–2017
Fluoride
188.5 µg/L 4.7%
of the EPA limit 4000 µg/L
worst single sample: 190 µg/L
2/2 SYR4 2014–2017
Selenium
2.08 µg/L 4.2%
of the EPA limit 50 µg/L
worst single sample: 2.1 µg/L
2/2 SYR4 2014–2017
Atrazine
1.5 µg/L 50%
of the EPA limit 3 µg/L
1/2 SYR4 2014–2017
Chromium
2.5 µg/L 2.5%
of the EPA limit 100 µg/L
1/2 SYR4 2014–2017
Combined Radium (-226 And -228)
1.7 pCi/L 34%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
30 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideEthylbenzeneMercuryMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MURPHY, JULIE
Phone
785-461-5886
Email
[email protected]

Frequently asked questions about Wakefield, City of

Is Wakefield, City of tap water safe to drink?

EPA monitoring detected 20 contaminants in Wakefield, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wakefield, City of's water?

EPA monitoring detected Copper, Nitrate, Lead, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Wakefield, City of serve?

Wakefield, City of reports serving 846 people in Kansas, per its EPA record.

Has Wakefield, City of had any water quality violations?

The EPA has 51 violations on file for Wakefield, City of, of which 12 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.