← Kansas

Tap water quality report

Bourbon Co Rwd 2c

EPA monitoring tested this supplier for 44 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
13
detected
7,050
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Bourbon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
26
violations on file
2
still open
ViolationTypeStatusPeriod
RPT Monitoring Unaddressed 2025-07-02
RPT Monitoring Unaddressed 2025-07-02
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31
MR Monitoring Resolved 2020-10-01 → 2020-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
564.5 µg/L 43%
of the EPA limit 1300 µg/L
worst single sample: 1200 µg/L
60/60 SYR4 2013–2019
Lead
13.8 µg/L 92%
of the EPA limit 15 µg/L
worst single sample: 31 µg/L
33/60 SYR4 2013–2019
Chloroform
91.85 µg/L
No EPA limit set
worst single sample: 110 µg/L
32/32 SYR4 2013–2019
Dichloroacetic Acid
63.9 µg/L
No EPA limit set
worst single sample: 84 µg/L
27/32 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
150 µg/L 250%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 190 µg/L
26/32 SYR4 2013–2019
Bromodichloromethane
11.9 µg/L
No EPA limit set
worst single sample: 12 µg/L
23/32 SYR4 2013–2019
TTHM
116.9 µg/L 146%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 120 µg/L
23/32 SYR4 2013–2019
Monobromoacetic Acid
1.028 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
17/32 SYR4 2013–2019
Monochloroacetic Acid
11.2 µg/L
No EPA limit set
worst single sample: 12 µg/L
17/32 SYR4 2013–2019
Trichloroacetic Acid
92.25 µg/L
No EPA limit set
worst single sample: 96 µg/L
16/32 SYR4 2013–2019
Dibromoacetic Acid
1.43 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
15/32 SYR4 2013–2019
Lead
0.0038 mg/L 25%
of the EPA limit 0.0150 mg/L
12/12 LCR 2025
Dibromochloromethane
2.72 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
5/32 SYR4 2013–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
POLLMEIER, MARK
Phone
620-223-1110
Email
[email protected]

Frequently asked questions about Bourbon Co Rwd 2c

Is Bourbon Co Rwd 2c tap water safe to drink?

EPA monitoring detected 13 contaminants in Bourbon Co Rwd 2c's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bourbon Co Rwd 2c's water?

EPA monitoring detected Copper, Lead, Chloroform, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Bourbon Co Rwd 2c serve?

Bourbon Co Rwd 2c reports serving 7,050 people in Kansas, per its EPA record.

Has Bourbon Co Rwd 2c had any water quality violations?

The EPA has 26 violations on file for Bourbon Co Rwd 2c, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.