Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2006-09-01 → 2006-09-30 |
| MR | Monitoring | Resolved | 2006-09-01 → 2006-09-30 |
| MR | Monitoring | Resolved | 2006-09-01 → 2006-09-30 |
| MR | Monitoring | Resolved | 2006-09-01 → 2006-09-30 |
| MR | Monitoring | Resolved | 1994-01-01 → 1994-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 803 µg/L 80% of the EPA limit 1000 µg/L
worst single sample: 980 µg/L | 239/240 | SYR4 | 2012–2019 |
| Fluoride | 921 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 990 µg/L | 40/40 | SYR4 | 2012–2019 |
| Bromodichloromethane | 25.1 µg/L No EPA limit set
worst single sample: 26 µg/L | 39/39 | SYR4 | 2012–2019 |
| Chloroform | 48 µg/L No EPA limit set
worst single sample: 61 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 16 µg/L No EPA limit set | 39/39 | SYR4 | 2012–2019 |
| TTHM | 73.1 µg/L 91% of the EPA limit 80 µg/L
worst single sample: 83 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 51 µg/L No EPA limit set
worst single sample: 57 µg/L | 38/38 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 82.75 µg/L 138% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 100 µg/L | 38/38 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 19 µg/L No EPA limit set
worst single sample: 36 µg/L | 38/38 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.42 µg/L No EPA limit set
worst single sample: 9.4 µg/L | 37/38 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 13.2 µg/L No EPA limit set
worst single sample: 16 µg/L | 30/38 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.62 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 29/38 | SYR4 | 2012–2019 |
| Nitrate | 940 µg/L 9.4% of the EPA limit 10000 µg/L
worst single sample: 970 µg/L | 26/32 | SYR4 | 2012–2019 |
| Bromoform | 4.79 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 23/39 | SYR4 | 2012–2019 |
| Atrazine | 4.075 µg/L 136% of the EPA limit, at the 95th percentile of samples — 3 µg/L
worst single sample: 4.9 µg/L | 12/16 | SYR4 | 2012–2019 |
| Barium | 99.65 µg/L 5% of the EPA limit 2000 µg/L
worst single sample: 100 µg/L | 8/8 | SYR4 | 2012–2019 |
| Copper | 13.95 µg/L 1.1% of the EPA limit 1300 µg/L
worst single sample: 15 µg/L | 8/8 | SYR4 | 2012–2019 |
| Arsenic | 1.185 µg/L 12% of the EPA limit 10 µg/L
worst single sample: 1.2 µg/L | 4/8 | SYR4 | 2012–2019 |
| Carbon Tetrachloride | 0.6890 µg/L 14% of the EPA limit 5 µg/L
worst single sample: 0.6900 µg/L | 3/5 | SYR4 | 2013–2017 |
| Chromium | 1.295 µg/L 1.3% of the EPA limit 100 µg/L
worst single sample: 1.3 µg/L | 2/8 | SYR4 | 2012–2019 |
| Selenium | 1.19 µg/L 2.4% of the EPA limit 50 µg/L
worst single sample: 1.2 µg/L | 2/8 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.1000 pCi/L 2% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2014 |
| Lasso | 0.2900 µg/L 14% of the EPA limit 2 µg/L | 1/16 | SYR4 | 2012–2019 |
40 contaminants tested, none detected
Utility contact
Frequently asked questions about Public Wholesale Wsd 5
Is Public Wholesale Wsd 5 tap water safe to drink?
EPA monitoring detected 23 contaminants in Public Wholesale Wsd 5's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Public Wholesale Wsd 5's water?
EPA monitoring detected Chlorite, Fluoride, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Public Wholesale Wsd 5 serve?
Public Wholesale Wsd 5 reports serving 1 people in Kansas, per its EPA record.
Has Public Wholesale Wsd 5 had any water quality violations?
The EPA has 5 violations on file for Public Wholesale Wsd 5, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.