← Kansas

Tap water quality report

Humboldt, City of

EPA monitoring tested this supplier for 63 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

63
contaminants tested
23
detected
1,836
people served
17
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Allen

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

17
health-based violations
30
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-02-01 → 2015-02-28
MCL Health-based Resolved 2015-02-01 → 2015-02-28
MCL Health-based Resolved 2015-02-01 → 2015-02-28
MCL Health-based Resolved 2015-02-01 → 2015-02-28
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
TT Health-based Resolved 1998-02-01 → 1998-02-28

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
926.5 µg/L 93%
of the EPA limit 1000 µg/L
worst single sample: 1100 µg/L
208/210 SYR4 2012–2019
Copper
343 µg/L 26%
of the EPA limit 1300 µg/L
worst single sample: 430 µg/L
38/38 SYR4 2012–2019
Bromodichloromethane
8.2 µg/L
No EPA limit set
worst single sample: 9.8 µg/L
33/33 SYR4 2012–2019
Chloroform
28.4 µg/L
No EPA limit set
worst single sample: 29 µg/L
33/33 SYR4 2012–2019
TTHM
35.8 µg/L 45%
of the EPA limit 80 µg/L
worst single sample: 38 µg/L
33/33 SYR4 2012–2019
Dichloroacetic Acid
41.35 µg/L
No EPA limit set
worst single sample: 47 µg/L
32/32 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
62.6 µg/L 104%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 74 µg/L
32/32 SYR4 2012–2019
Trichloroacetic Acid
14.45 µg/L
No EPA limit set
worst single sample: 18 µg/L
32/32 SYR4 2012–2019
Dibromochloromethane
3.95 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
31/33 SYR4 2012–2019
Nitrate
1410 µg/L 14%
of the EPA limit 10000 µg/L
worst single sample: 1500 µg/L
30/32 SYR4 2012–2019
Dibromoacetic Acid
4.03 µg/L
No EPA limit set
worst single sample: 6.8 µg/L
28/32 SYR4 2012–2019
Monochloroacetic Acid
9.9 µg/L
No EPA limit set
worst single sample: 11 µg/L
21/32 SYR4 2012–2019
Monobromoacetic Acid
2.075 µg/L
No EPA limit set
worst single sample: 2.5 µg/L
18/32 SYR4 2012–2019
Atrazine
2.135 µg/L 71%
of the EPA limit 3 µg/L
worst single sample: 3.5 µg/L
14/16 SYR4 2012–2019
Lead
5.98 µg/L 40%
of the EPA limit 15 µg/L
worst single sample: 6.5 µg/L
14/38 SYR4 2012–2019
Bromoform
1.5 µg/L
No EPA limit set
9/33 SYR4 2012–2019
Barium
133 µg/L 6.7%
of the EPA limit 2000 µg/L
worst single sample: 140 µg/L
8/8 SYR4 2012–2019
Lead
0.0017 mg/L 11%
of the EPA limit 0.0150 mg/L
7/7 LCR 2025
Fluoride
260 µg/L 6.5%
of the EPA limit 4000 µg/L
worst single sample: 270 µg/L
5/8 SYR4 2012–2019
Selenium
1.88 µg/L 3.8%
of the EPA limit 50 µg/L
worst single sample: 2 µg/L
5/8 SYR4 2012–2019
Chromium
2.505 µg/L 2.5%
of the EPA limit 100 µg/L
worst single sample: 2.7 µg/L
4/8 SYR4 2012–2019
Arsenic
1.95 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
3/8 SYR4 2012–2019
Combined Radium (-226 And -228)
0.4000 pCi/L 8%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
40 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DEAN, JONATHAN C
Phone
620-473-3131
Email
[email protected]

Frequently asked questions about Humboldt, City of

Is Humboldt, City of tap water safe to drink?

EPA monitoring detected 23 contaminants in Humboldt, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Humboldt, City of's water?

EPA monitoring detected Chlorite, Copper, Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Humboldt, City of serve?

Humboldt, City of reports serving 1,836 people in Kansas, per its EPA record.

Has Humboldt, City of had any water quality violations?

The EPA has 30 violations on file for Humboldt, City of, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.