← Indiana

Tap water quality report

Indiana American Water - Richmond

EPA monitoring tested this supplier for 101 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

101
contaminants tested
13
detected
41,485
people served
0
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Wayne

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
9
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-10-01 → 1981-09-30
MR Monitoring Archived 1980-06-30 → 1980-09-29

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
76.8 µg/L 96%
of the EPA limit 80 µg/L
worst single sample: 102.2 µg/L
162/162 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
29.23 µg/L 49%
of the EPA limit 60 µg/L
worst single sample: 34.5 µg/L
162/162 SYR4 2012–2019
Nitrate
4360 µg/L 44%
of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L
48/48 SYR4 2012–2019
Atrazine
0.8000 µg/L 27%
of the EPA limit 3 µg/L
worst single sample: 3 µg/L
33/83 SYR4 2012–2019
Copper
911.35 µg/L 70%
of the EPA limit 1300 µg/L
worst single sample: 1191 µg/L
28/30 SYR4 2017
Lead
11.7 µg/L 78%
of the EPA limit 15 µg/L
worst single sample: 14 µg/L
24/30 SYR4 2017
Fluoride
896 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 950 µg/L
19/19 SYR4 2012–2019
Nitrate-Nitrite
4426 µg/L 44%
of the EPA limit 10000 µg/L
worst single sample: 4800 µg/L
18/18 SYR4 2013–2019
Lead
0.0040 mg/L 27%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Simazine
0.4110 µg/L 10%
of the EPA limit 4 µg/L
worst single sample: 0.4300 µg/L
3/82 SYR4 2012–2019
Endrin
0.0900 µg/L 4.5%
of the EPA limit 2 µg/L
1/83 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
0.9900 pCi/L 6.6%
of the EPA limit 15 pCi/L
1/1 SYR4 2016
Tetrachloroethylene
2.4 µg/L 48%
of the EPA limit 5 µg/L
1/23 SYR4 2012–2019
88 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GOSNELL, CHRISTINA
Phone
317-885-2408
Email
[email protected]

Frequently asked questions about Indiana American Water - Richmond

Is Indiana American Water - Richmond tap water safe to drink?

EPA monitoring detected 13 contaminants in Indiana American Water - Richmond's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Indiana American Water - Richmond's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Nitrate, Atrazine, Copper, and others. The full list with the level and data source for each is above.

How many people does Indiana American Water - Richmond serve?

Indiana American Water - Richmond reports serving 41,485 people in Indiana, per its EPA record.

Has Indiana American Water - Richmond had any water quality violations?

The EPA has 9 violations on file for Indiana American Water - Richmond, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.