← Indiana

Tap water quality report

German Township Water District Inc.

EPA monitoring tested this supplier for 35 contaminants and detected 6. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

35
contaminants tested
6
detected
12,890
people served
32
health-based violations
Water source
SWP
Ownership
Private
Counties served
Vanderburgh

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

32
health-based violations
43
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-07-01 → 2015-07-31
MCL Health-based Resolved 2015-07-01 → 2015-07-31
MCL Health-based Resolved 2015-07-01 → 2015-07-31
MCL Health-based Resolved 2015-07-01 → 2015-07-31
MCL Health-based Resolved 2015-07-01 → 2015-07-31
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30
MCL Health-based Resolved 2014-07-01 → 2014-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfpea 0.0085 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
83.5 µg/L 104%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 160 µg/L
124/124 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
52 µg/L 87%
of the EPA limit 60 µg/L
worst single sample: 150 µg/L
121/124 SYR4 2012–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Copper
42.6 µg/L 3.3%
of the EPA limit 1300 µg/L
worst single sample: 43 µg/L
5/30 SYR4 2017
Lead
7.85 µg/L 52%
of the EPA limit 15 µg/L
worst single sample: 8.1 µg/L
3/30 SYR4 2017
29 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
MOUNT, GAYLENE
Phone
812-963-6403
Email
[email protected]

Frequently asked questions about German Township Water District Inc.

Is German Township Water District Inc. tap water safe to drink?

EPA monitoring detected 6 contaminants in German Township Water District Inc.'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in German Township Water District Inc.'s water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Copper, Lead, and others. The full list with the level and data source for each is above.

How many people does German Township Water District Inc. serve?

German Township Water District Inc. reports serving 12,890 people in Indiana, per its EPA record.

Has German Township Water District Inc. had any water quality violations?

The EPA has 43 violations on file for German Township Water District Inc., of which 32 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.