Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Unaddressed | 2025-10-01 |
| Other | Monitoring | Unaddressed | 2025-07-01 |
| MR | Monitoring | Resolved | 2024-07-01 → 2024-09-30 |
| MR | Monitoring | Resolved | 2024-07-01 → 2024-09-30 |
| Other | Monitoring | Resolved | 2024-07-01 |
| Other | Monitoring | Resolved | 2024-07-01 |
| Other | Monitoring | Resolved | 2024-07-01 |
| MR | Monitoring | Resolved | 2024-07-01 → 2024-09-30 |
| MON | Monitoring | Resolved | 2024-03-01 → 2024-03-31 |
| MON | Monitoring | Resolved | 2024-03-01 → 2024-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5100 µg/L 51% of the EPA limit 10000 µg/L
worst single sample: 5900 µg/L | 50/52 | SYR4 | 2012–2019 |
| Lead | 0.0027 mg/L 18% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2025 |
| TTHM | 21.42 µg/L 27% of the EPA limit 80 µg/L
worst single sample: 23.4 µg/L | 10/10 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 8.43 µg/L 14% of the EPA limit 60 µg/L
worst single sample: 8.7 µg/L | 7/10 | SYR4 | 2012–2018 |
| Barium | 81.5 µg/L 4.1% of the EPA limit 2000 µg/L
worst single sample: 86 µg/L | 6/6 | SYR4 | 2014–2017 |
| Copper | 220 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 250 µg/L | 6/6 | SYR4 | 2018 |
| Arsenic | 1.96 µg/L 20% of the EPA limit 10 µg/L
worst single sample: 2 µg/L | 5/6 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 4540 µg/L 45% of the EPA limit 10000 µg/L
worst single sample: 4600 µg/L | 5/6 | SYR4 | 2014–2017 |
| Chromium | 1.48 µg/L 1.5% of the EPA limit 100 µg/L
worst single sample: 1.5 µg/L | 2/6 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 1.26 pCi/L 8.4% of the EPA limit 15 pCi/L
worst single sample: 1.3 pCi/L | 2/2 | SYR4 | 2018 |
| Chloroform | 1 µg/L No EPA limit set | 1/6 | SYR4 | 2014–2017 |
| Lead | 2.6 µg/L 17% of the EPA limit 15 µg/L | 1/6 | SYR4 | 2018 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Kingsbury Utility Corporation
Is Kingsbury Utility Corporation tap water safe to drink?
EPA monitoring detected 12 contaminants in Kingsbury Utility Corporation's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Kingsbury Utility Corporation's water?
EPA monitoring detected Nitrate, Lead, TTHM, Total Haloacetic Acids (HAA5), Barium, and others. The full list with the level and data source for each is above.
How many people does Kingsbury Utility Corporation serve?
Kingsbury Utility Corporation reports serving 240 people in Indiana, per its EPA record.
Has Kingsbury Utility Corporation had any water quality violations?
The EPA has 242 violations on file for Kingsbury Utility Corporation, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.