Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 2011-02-01 → 2011-02-28 |
| MCL | Health-based | Resolved | 1999-05-01 → 1999-05-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 32.8 µg/L 41% of the EPA limit 80 µg/L
worst single sample: 39 µg/L | 125/125 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 13.355 µg/L 22% of the EPA limit 60 µg/L
worst single sample: 27 µg/L | 124/125 | SYR4 | 2012–2019 |
| Copper | 272.1 µg/L 21% of the EPA limit 1300 µg/L
worst single sample: 275 µg/L | 30/30 | SYR4 | 2017 |
| Lead | 2.29 µg/L 15% of the EPA limit 15 µg/L
worst single sample: 2.5 µg/L | 23/30 | SYR4 | 2017 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2024 |
| Nitrate | 1700 µg/L 17% of the EPA limit 10000 µg/L | 14/14 | SYR4 | 2012–2018 |
| Barium | 24.235 µg/L 1.2% of the EPA limit 2000 µg/L
worst single sample: 24.6 µg/L | 2/2 | SYR4 | 2014–2017 |
| Fluoride | 890 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 900 µg/L | 2/2 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 570 µg/L 5.7% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
90 contaminants tested, none detected
Utility contact
Frequently asked questions about Jackson County Water Utility
Is Jackson County Water Utility tap water safe to drink?
EPA monitoring detected 11 contaminants in Jackson County Water Utility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jackson County Water Utility's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Lead, Lead, and others. The full list with the level and data source for each is above.
How many people does Jackson County Water Utility serve?
Jackson County Water Utility reports serving 13,667 people in Indiana, per its EPA record.
Has Jackson County Water Utility had any water quality violations?
The EPA has 705 violations on file for Jackson County Water Utility, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.