Tap water quality report

Southeast Joliet Sd

EPA monitoring tested this supplier for 78 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
17
detected
2,000
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Will

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
345
violations on file
15
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
MCL Health-based Archived 1999-05-01 → 1999-05-31
MCL Health-based Archived 1999-05-01 → 1999-05-31
MCL Health-based Archived 1993-11-01 → 1993-11-30
MCL Health-based Archived 1993-11-01 → 1993-11-30
MCL Health-based Archived 1993-11-01 → 1993-11-30
MCL Health-based Archived 1993-11-01 → 1993-11-30
MCL Health-based Archived 1993-11-01 → 1993-11-30
MCL Health-based Archived 1993-11-01 → 1993-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2022
Bromodichloromethane
15.48 µg/L
No EPA limit set
worst single sample: 16 µg/L
9/9 SYR4 2013–2019
Copper
695 µg/L 53%
of the EPA limit 1300 µg/L
worst single sample: 881 µg/L
9/30 SYR4 2013–2019
Chloroform
33.4 µg/L
No EPA limit set
worst single sample: 33.6 µg/L
9/9 SYR4 2013–2019
Dibromochloromethane
9.86 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
9/9 SYR4 2013–2019
TTHM
57.22 µg/L 72%
of the EPA limit 80 µg/L
worst single sample: 57.7 µg/L
9/9 SYR4 2013–2019
Dibromoacetic Acid
1.585 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
4/9 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
23.955 µg/L 40%
of the EPA limit 60 µg/L
worst single sample: 24 µg/L
4/9 SYR4 2013–2019
Trichloroacetic Acid
9.755 µg/L
No EPA limit set
worst single sample: 9.8 µg/L
4/9 SYR4 2013–2019
Barium
57.52 µg/L 2.9%
of the EPA limit 2000 µg/L
worst single sample: 58.2 µg/L
3/3 SYR4 2012–2018
Dichloroacetic Acid
12.69 µg/L
No EPA limit set
worst single sample: 12.7 µg/L
3/9 SYR4 2013–2019
Fluoride
1410 µg/L 35%
of the EPA limit 4000 µg/L
worst single sample: 1440 µg/L
3/3 SYR4 2012–2018
Arsenic
0.6511 µg/L 6.5%
of the EPA limit 10 µg/L
worst single sample: 0.6520 µg/L
2/3 SYR4 2012–2018
Bromoform
4.625 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
2/9 SYR4 2013–2019
Combined Radium (-226 And -228)
1.097 pCi/L 22%
of the EPA limit 5 pCi/L
worst single sample: 1.12 pCi/L
2/2 SYR4 2012–2018
Nitrate
40 µg/L 0.4%
of the EPA limit 10000 µg/L
2/22 SYR4 2012–2019
Lead
28.7 µg/L 191%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
1/30 SYR4 2013–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about Southeast Joliet Sd

Is Southeast Joliet Sd tap water safe to drink?

EPA monitoring detected 17 contaminants in Southeast Joliet Sd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Southeast Joliet Sd's water?

EPA monitoring detected Lead, Bromodichloromethane, Copper, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Southeast Joliet Sd serve?

Southeast Joliet Sd reports serving 2,000 people, per its EPA record.

Has Southeast Joliet Sd had any water quality violations?

The EPA has 345 violations on file for Southeast Joliet Sd, of which 12 are health-based (a contaminant limit or required treatment was breached) and 15 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.