← Illinois

Tap water quality report

Gateway Mhp

EPA monitoring tested this supplier for 49 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

49
contaminants tested
16
detected
884
people served
2
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Will

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
8
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 1994-01-01
TT Health-based Resolved 1994-01-01
MR Monitoring Resolved 1994-04-01 → 1994-06-30
MR Monitoring Resolved 1994-04-01 → 1994-06-30
MR Monitoring Resolved 1994-04-01 → 1994-06-30
MR Monitoring Resolved 1994-04-01 → 1994-06-30
MR Monitoring Resolved 1994-04-01 → 1994-06-30
MR Monitoring Resolved 1994-04-01 → 1994-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
19/19 LCR 2025
Copper
594.9 µg/L 46%
of the EPA limit 1300 µg/L
worst single sample: 669 µg/L
14/30 SYR4 2013–2019
Dichloroacetic Acid
7.5785 µg/L
No EPA limit set
worst single sample: 9.78 µg/L
8/12 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
10.6365 µg/L 18%
of the EPA limit 60 µg/L
worst single sample: 12.67 µg/L
8/12 SYR4 2013–2019
Fluoride
1891 µg/L 47%
of the EPA limit 4000 µg/L
worst single sample: 2260 µg/L
7/7 SYR4 2012–2018
Arsenic
8.0175 µg/L 80%
of the EPA limit 10 µg/L
worst single sample: 8.02 µg/L
6/6 SYR4 2012–2018
Barium
68.875 µg/L 3.4%
of the EPA limit 2000 µg/L
worst single sample: 70.2 µg/L
6/6 SYR4 2012–2018
Nitrate
58 µg/L 0.6%
of the EPA limit 10000 µg/L
6/32 SYR4 2012–2019
Combined Radium (-226 And -228)
4.676 pCi/L 94%
of the EPA limit 5 pCi/L
worst single sample: 4.8 pCi/L
5/5 SYR4 2012–2018
Chloroform
7.873 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
3/12 SYR4 2013–2019
TTHM
8.018 µg/L 10%
of the EPA limit 80 µg/L
worst single sample: 8.2 µg/L
3/12 SYR4 2013–2019
Lead
14.7305 µg/L 98%
of the EPA limit 15 µg/L
worst single sample: 15.1 µg/L
2/30 SYR4 2013–2019
Nitrate-Nitrite
54.95 µg/L 0.5%
of the EPA limit 10000 µg/L
worst single sample: 55 µg/L
2/8 SYR4 2012–2016
Trichloroacetic Acid
3.2815 µg/L
No EPA limit set
worst single sample: 3.37 µg/L
2/12 SYR4 2013–2019
Bromodichloromethane
1.45 µg/L
No EPA limit set
1/12 SYR4 2013–2019
Monochloroacetic Acid
2.89 µg/L
No EPA limit set
1/12 SYR4 2013–2019
33 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbon TetrachlorideChromiumDichloromethaneDibromoacetic AcidDibromochloromethaneEthylbenzeneMercuryMonobromoacetic AcidNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JESSEN, DIANNA
Phone
815-469-1998
Email
[email protected]

Frequently asked questions about Gateway Mhp

Is Gateway Mhp tap water safe to drink?

EPA monitoring detected 16 contaminants in Gateway Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Gateway Mhp's water?

EPA monitoring detected Lead, Copper, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Fluoride, and others. The full list with the level and data source for each is above.

How many people does Gateway Mhp serve?

Gateway Mhp reports serving 884 people in Illinois, per its EPA record.

Has Gateway Mhp had any water quality violations?

The EPA has 8 violations on file for Gateway Mhp, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.