← Illinois

Tap water quality report

Curran-Gardner Township Pwd

EPA monitoring tested this supplier for 109 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
17
detected
6,651
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Sangamon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
4
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2008-06-01 → 2008-06-30
MCL Health-based Resolved 2008-06-01 → 2008-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
16.34 µg/L
No EPA limit set
worst single sample: 21.9 µg/L
45/45 SYR4 2012–2019
Dibromoacetic Acid
9.5 µg/L
No EPA limit set
worst single sample: 11.4 µg/L
45/45 SYR4 2012–2019
Dibromochloromethane
31.68 µg/L
No EPA limit set
worst single sample: 36.1 µg/L
45/45 SYR4 2012–2019
TTHM
84.06 µg/L 105%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 100.5 µg/L
45/45 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
12.16 µg/L 20%
of the EPA limit 60 µg/L
worst single sample: 14.2 µg/L
45/45 SYR4 2012–2019
Bromoform
44.76 µg/L
No EPA limit set
worst single sample: 53.1 µg/L
44/45 SYR4 2012–2019
Chloroform
7.85 µg/L
No EPA limit set
worst single sample: 10.6 µg/L
35/45 SYR4 2012–2019
Dichloroacetic Acid
3.245 µg/L
No EPA limit set
worst single sample: 3.6 µg/L
32/45 SYR4 2012–2019
Nitrate
3283 µg/L 33%
of the EPA limit 10000 µg/L
worst single sample: 3330 µg/L
22/24 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Nitrate-Nitrite
2860 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 3330 µg/L
11/12 SYR4 2012–2019
Monobromoacetic Acid
1.37 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
7/45 SYR4 2012–2019
Trichloroacetic Acid
1.41 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
7/45 SYR4 2012–2019
Barium
14.941 µg/L 0.7%
of the EPA limit 2000 µg/L
worst single sample: 15.5 µg/L
3/3 SYR4 2012–2018
Fluoride
1046.1 µg/L 26%
of the EPA limit 4000 µg/L
worst single sample: 1080 µg/L
3/3 SYR4 2012–2018
Lead
5.87 µg/L 39%
of the EPA limit 15 µg/L
1/40 SYR4 2014–2017
Selenium
2.48 µg/L 5%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
92 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCopperCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SMITH, AARON
Phone
217-546-3981
Email
[email protected]

Frequently asked questions about Curran-Gardner Township Pwd

Is Curran-Gardner Township Pwd tap water safe to drink?

EPA monitoring detected 17 contaminants in Curran-Gardner Township Pwd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Curran-Gardner Township Pwd's water?

EPA monitoring detected Bromodichloromethane, Dibromoacetic Acid, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Curran-Gardner Township Pwd serve?

Curran-Gardner Township Pwd reports serving 6,651 people in Illinois, per its EPA record.

Has Curran-Gardner Township Pwd had any water quality violations?

The EPA has 4 violations on file for Curran-Gardner Township Pwd, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.