← Illinois

Tap water quality report

New Athens

EPA monitoring tested this supplier for 14 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
14
detected
1,970
people served
5
health-based violations
Water source
SWP
Ownership
Local government
Counties served
St. Clair

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
42
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2018-01-01 → 2018-01-31
TT Health-based Resolved 2018-01-01 → 2018-01-31
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2024-07-01
Other Monitoring Resolved 2023-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
18.6 µg/L
No EPA limit set
worst single sample: 19.8 µg/L
53/53 SYR4 2012–2019
Chloroform
75.14 µg/L
No EPA limit set
worst single sample: 81.2 µg/L
53/53 SYR4 2012–2019
TTHM
93.74 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 96.68 µg/L
53/53 SYR4 2012–2019
Dibromochloromethane
7.14 µg/L
No EPA limit set
worst single sample: 8.5 µg/L
49/53 SYR4 2012–2019
Dichloroacetic Acid
27.8 µg/L
No EPA limit set
worst single sample: 35.2 µg/L
49/53 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
55.06 µg/L 92%
of the EPA limit 60 µg/L
worst single sample: 68.9 µg/L
49/53 SYR4 2012–2019
Trichloroacetic Acid
28.72 µg/L
No EPA limit set
worst single sample: 33.7 µg/L
48/53 SYR4 2012–2019
Copper
655.6 µg/L 50%
of the EPA limit 1300 µg/L
worst single sample: 1190 µg/L
17/30 SYR4 2013–2019
Lead
0.0052 mg/L 35%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Dibromoacetic Acid
1.75 µg/L
No EPA limit set
worst single sample: 1.8 µg/L
11/53 SYR4 2012–2019
Monochloroacetic Acid
4.455 µg/L
No EPA limit set
worst single sample: 4.8 µg/L
4/53 SYR4 2012–2019
Bromoform
1 µg/L
No EPA limit set
2/53 SYR4 2012–2019
Lead
6.7 µg/L 45%
of the EPA limit 15 µg/L
1/30 SYR4 2013–2019
Monobromoacetic Acid
1.3 µg/L
No EPA limit set
1/53 SYR4 2012–2019

Utility contact

Contact
BEHNKEN, JOE
Phone
618-604-3262
Email
[email protected]

Frequently asked questions about New Athens

Is New Athens tap water safe to drink?

EPA monitoring detected 14 contaminants in New Athens's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in New Athens's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dibromochloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does New Athens serve?

New Athens reports serving 1,970 people in Illinois, per its EPA record.

Has New Athens had any water quality violations?

The EPA has 42 violations on file for New Athens, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.