Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2024-07-01 |
| Other | Monitoring | Resolved | 2024-07-01 |
| MR | Monitoring | Resolved | 2023-10-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-10-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-10-01 → 2023-12-31 |
| MR | Monitoring | Resolved | 2023-10-01 → 2023-12-31 |
| MR | Monitoring | Archived | 1993-09-01 → 1993-09-30 |
| MR | Monitoring | Archived | 1977-06-30 → 1981-06-29 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0220 µg/L | 4/4 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 16.729 µg/L No EPA limit set
worst single sample: 25.49 µg/L | 107/107 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.58 µg/L No EPA limit set
worst single sample: 39.7 µg/L | 107/107 | SYR4 | 2012–2019 |
| TTHM | 17.518 µg/L 22% of the EPA limit 80 µg/L
worst single sample: 26.06 µg/L | 107/107 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 33.88 µg/L 56% of the EPA limit 60 µg/L
worst single sample: 44.9 µg/L | 107/107 | SYR4 | 2012–2019 |
| Copper | 172 µg/L 13% of the EPA limit 1300 µg/L
worst single sample: 390 µg/L | 58/60 | SYR4 | 2014–2017 |
| Bromodichloromethane | 1.6602 µg/L No EPA limit set
worst single sample: 1.922 µg/L | 54/107 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 5.025 µg/L No EPA limit set
worst single sample: 5.3 µg/L | 46/107 | SYR4 | 2012–2019 |
| Lead | 30.75 µg/L 205% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 57 µg/L | 26/60 | SYR4 | 2014–2017 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 22/22 | LCR | 2025 |
| Monobromoacetic Acid | 11.33 µg/L No EPA limit set
worst single sample: 12.5 µg/L | 19/107 | SYR4 | 2012–2019 |
| Nitrate | 3200 µg/L 32% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 38 µg/L 1.9% of the EPA limit 2000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1182.5 µg/L 30% of the EPA limit 4000 µg/L
worst single sample: 1200 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.631 µg/L No EPA limit set
worst single sample: 5.03 µg/L | 8/107 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 2500 µg/L 25% of the EPA limit 10000 µg/L
worst single sample: 2600 µg/L | 3/3 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 1.265 pCi/L 25% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2015 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Moline
Is Moline tap water safe to drink?
EPA monitoring detected 17 contaminants in Moline's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Moline's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.
How many people does Moline serve?
Moline reports serving 44,500 people in Illinois, per its EPA record.
Has Moline had any water quality violations?
The EPA has 8 violations on file for Moline, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.