Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-04-02 |
| TT | Health-based | Resolved | 2023-04-02 |
| TT | Health-based | Resolved | 2023-04-02 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 181.5 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 650 µg/L | 58/60 | SYR4 | 2013–2019 |
| Bromodichloromethane | 13.92 µg/L No EPA limit set
worst single sample: 15.2 µg/L | 57/57 | SYR4 | 2012–2019 |
| Chloroform | 92.962 µg/L No EPA limit set
worst single sample: 100 µg/L | 57/57 | SYR4 | 2012–2019 |
| TTHM | 106.82 µg/L 134% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 116.15 µg/L | 57/57 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 70.58 µg/L 118% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 90.6 µg/L | 57/57 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 45.38 µg/L No EPA limit set
worst single sample: 54.8 µg/L | 57/57 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.3324 µg/L No EPA limit set
worst single sample: 3.4 µg/L | 52/57 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 32.14 µg/L No EPA limit set
worst single sample: 36.3 µg/L | 43/57 | SYR4 | 2012–2019 |
| Lead | 15 µg/L 100% of the EPA limit 15 µg/L
worst single sample: 30 µg/L | 41/60 | SYR4 | 2013–2019 |
| Lead | 0.0037 mg/L 25% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2025 |
| Nitrate | 340 µg/L 3.4% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Arsenic | 3.8 µg/L 38% of the EPA limit 10 µg/L | 8/8 | SYR4 | 2012–2019 |
| Barium | 33.85 µg/L 1.7% of the EPA limit 2000 µg/L
worst single sample: 37 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1196 µg/L 30% of the EPA limit 4000 µg/L
worst single sample: 1210 µg/L | 8/8 | SYR4 | 2012–2019 |
| Atrazine | 1.118 µg/L 37% of the EPA limit 3 µg/L
worst single sample: 1.3 µg/L | 5/25 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.61 µg/L No EPA limit set
worst single sample: 3.63 µg/L | 5/57 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 161 µg/L 1.6% of the EPA limit 10000 µg/L
worst single sample: 170 µg/L | 3/3 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 0.4910 pCi/L 9.8% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2014 |
| Monobromoacetic Acid | 1.07 µg/L No EPA limit set | 1/57 | SYR4 | 2012–2019 |
90 contaminants tested, none detected
Utility contact
Frequently asked questions about Holiday Shores Sd
Is Holiday Shores Sd tap water safe to drink?
EPA monitoring detected 19 contaminants in Holiday Shores Sd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Holiday Shores Sd's water?
EPA monitoring detected Copper, Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Holiday Shores Sd serve?
Holiday Shores Sd reports serving 2,840 people in Illinois, per its EPA record.
Has Holiday Shores Sd had any water quality violations?
The EPA has 111 violations on file for Holiday Shores Sd, of which 70 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.