← Illinois

Tap water quality report

Carlinville

EPA monitoring tested this supplier for 110 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
23
detected
6,598
people served
167
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Macoupin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

167
health-based violations
215
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-08-01 → 2015-08-31
TT Health-based Resolved 2015-07-01 → 2015-07-31
TT Health-based Resolved 2015-07-01 → 2015-07-31
TT Health-based Resolved 2015-07-01 → 2015-07-31
TT Health-based Resolved 2015-07-01 → 2015-07-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
892 µg/L 89%
of the EPA limit 1000 µg/L
worst single sample: 1300 µg/L
200/264 SYR4 2012–2019
Copper
164.9 µg/L 13%
of the EPA limit 1300 µg/L
worst single sample: 870 µg/L
138/180 SYR4 2014–2019
Chloroform
97.147 µg/L
No EPA limit set
worst single sample: 128.5 µg/L
58/58 SYR4 2012–2019
TTHM
103.192 µg/L 129%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 147.3 µg/L
57/57 SYR4 2012–2019
Bromodichloromethane
8.9141 µg/L
No EPA limit set
worst single sample: 16.04 µg/L
55/57 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
44.4 µg/L 74%
of the EPA limit 60 µg/L
worst single sample: 64.3 µg/L
45/57 SYR4 2012–2019
Trichloroacetic Acid
24.905 µg/L
No EPA limit set
worst single sample: 64.3 µg/L
44/57 SYR4 2012–2019
Dichloroacetic Acid
28.06 µg/L
No EPA limit set
worst single sample: 30 µg/L
37/57 SYR4 2012–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
29/29 LCR 2025
Lead
20.8 µg/L 139%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 22.7 µg/L
27/180 SYR4 2014–2019
Nitrate
1700 µg/L 17%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Atrazine
3.5 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 3 µg/L
worst single sample: 4.7 µg/L
13/33 SYR4 2012–2019
Barium
52.25 µg/L 2.6%
of the EPA limit 2000 µg/L
worst single sample: 55 µg/L
12/12 SYR4 2012–2019
Fluoride
899.25 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 957 µg/L
12/12 SYR4 2012–2019
Dibromochloromethane
2.90505 µg/L
No EPA limit set
worst single sample: 3.441 µg/L
10/57 SYR4 2012–2019
Simazine
2.56 µg/L 64%
of the EPA limit 4 µg/L
worst single sample: 2.7 µg/L
8/29 SYR4 2012–2019
Arsenic
2.38 µg/L 24%
of the EPA limit 10 µg/L
worst single sample: 2.5 µg/L
7/12 SYR4 2012–2019
Combined Radium (-226 And -228)
1.3162 pCi/L 26%
of the EPA limit 5 pCi/L
worst single sample: 1.33 pCi/L
4/6 SYR4 2015–2017
Nitrate-Nitrite
1470 µg/L 15%
of the EPA limit 10000 µg/L
worst single sample: 1500 µg/L
3/3 SYR4 2012–2019
Dibromoacetic Acid
1.494 µg/L
No EPA limit set
worst single sample: 1.51 µg/L
2/57 SYR4 2012–2019
Chromium
7.2 µg/L 7.2%
of the EPA limit 100 µg/L
1/12 SYR4 2012–2019
Monobromoacetic Acid
4.11 µg/L
No EPA limit set
1/57 SYR4 2012–2019
Monochloroacetic Acid
2.4 µg/L
No EPA limit set
1/57 SYR4 2012–2019
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromateBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HASARA, TIM
Phone
217-854-4076
Email
[email protected]

Frequently asked questions about Carlinville

Is Carlinville tap water safe to drink?

EPA monitoring detected 23 contaminants in Carlinville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Carlinville's water?

EPA monitoring detected Chlorite, Copper, Chloroform, TTHM, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Carlinville serve?

Carlinville reports serving 6,598 people in Illinois, per its EPA record.

Has Carlinville had any water quality violations?

The EPA has 215 violations on file for Carlinville, of which 167 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.