← Illinois

Tap water quality report

Chenoa

EPA monitoring tested this supplier for 81 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

81
contaminants tested
24
detected
1,785
people served
80
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
McLean

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

80
health-based violations
116
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-10-01 → 2023-12-31
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30
MCL Health-based Resolved 2023-07-01 → 2023-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
370 µg/L 28%
of the EPA limit 1300 µg/L
worst single sample: 879 µg/L
61/70 SYR4 2012–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
41/41 LCR 2025
Lead
42.4 µg/L 283%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 140 µg/L
37/70 SYR4 2012–2019
Combined Radium (-226 And -228)
8.178 pCi/L 164%
of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 21.5 pCi/L
35/38 SYR4 2012–2019
TTHM
95.74 µg/L 120%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 103.6 µg/L
23/23 SYR4 2012–2019
Bromoform
50.5 µg/L
No EPA limit set
worst single sample: 62.8 µg/L
22/23 SYR4 2012–2019
Dibromochloromethane
25.86 µg/L
No EPA limit set
worst single sample: 37.8 µg/L
22/23 SYR4 2012–2019
Nitrate
175 µg/L 1.8%
of the EPA limit 10000 µg/L
20/30 SYR4 2012–2019
Dibromoacetic Acid
23.15 µg/L
No EPA limit set
worst single sample: 31.7 µg/L
19/23 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
27.75 µg/L 46%
of the EPA limit 60 µg/L
worst single sample: 39 µg/L
19/23 SYR4 2012–2019
Bromodichloromethane
10.5305 µg/L
No EPA limit set
worst single sample: 13.8 µg/L
14/23 SYR4 2012–2019
Fluoride
2375 µg/L 59%
of the EPA limit 4000 µg/L
worst single sample: 2540 µg/L
12/12 SYR4 2012–2019
Barium
396.9 µg/L 20%
of the EPA limit 2000 µg/L
worst single sample: 420 µg/L
8/8 SYR4 2012–2018
Arsenic
30 µg/L 300%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 33.9 µg/L
7/8 SYR4 2012–2018
Chloroform
3.18 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
5/23 SYR4 2012–2019
Nitrate-Nitrite
171.2 µg/L 1.7%
of the EPA limit 10000 µg/L
worst single sample: 175 µg/L
5/10 SYR4 2012–2017
Selenium
11.46 µg/L 23%
of the EPA limit 50 µg/L
worst single sample: 12 µg/L
3/8 SYR4 2012–2018
Combined Uranium
0.0624 µg/L 0.2%
of the EPA limit 30 µg/L
worst single sample: 0.0641 µg/L
2/2 SYR4 2014
Dichloroacetic Acid
2.715 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
2/23 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
33.5479 pCi/L 224%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 34.479 pCi/L
2/2 SYR4 2014
Monobromoacetic Acid
4.4905 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
2/23 SYR4 2012–2019
2,4-D
7.1 µg/L 10%
of the EPA limit 70 µg/L
1/5 SYR4 2014–2017
Antimony, Total
3.8 µg/L 63%
of the EPA limit 6 µg/L
1/9 SYR4 2012–2018
Chromium
5.1 µg/L 5.1%
of the EPA limit 100 µg/L
1/8 SYR4 2012–2018
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TPAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHANE, DAVID
Phone
309-825-2396
Email
[email protected]

Frequently asked questions about Chenoa

Is Chenoa tap water safe to drink?

EPA monitoring detected 24 contaminants in Chenoa's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Chenoa's water?

EPA monitoring detected Copper, Lead, Lead, Combined Radium (-226 And -228), TTHM, and others. The full list with the level and data source for each is above.

How many people does Chenoa serve?

Chenoa reports serving 1,785 people in Illinois, per its EPA record.

Has Chenoa had any water quality violations?

The EPA has 116 violations on file for Chenoa, of which 80 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.