Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2012-08-01 → 2012-08-31 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-06-01 → 2005-06-30 |
| MCL | Health-based | Archived | 1997-07-01 → 1997-07-31 |
| MCL | Health-based | Archived | 1997-07-01 → 1997-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1505 µg/L 116% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2080 µg/L | 51/60 | SYR4 | 2014–2017 |
| Bromodichloromethane | 10.4035 µg/L No EPA limit set
worst single sample: 12.33 µg/L | 28/28 | SYR4 | 2012–2019 |
| Chloroform | 25.762 µg/L No EPA limit set
worst single sample: 26.76 µg/L | 28/28 | SYR4 | 2012–2019 |
| TTHM | 38.3115 µg/L 48% of the EPA limit 80 µg/L
worst single sample: 43.87 µg/L | 28/28 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 26.5 µg/L 44% of the EPA limit 60 µg/L
worst single sample: 28.3 µg/L | 28/28 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.9464 µg/L No EPA limit set
worst single sample: 8.898 µg/L | 27/28 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 13.01 µg/L No EPA limit set
worst single sample: 13.9 µg/L | 27/28 | SYR4 | 2012–2019 |
| Barium | 1380 µg/L 69% of the EPA limit 2000 µg/L
worst single sample: 2180 µg/L | 23/24 | SYR4 | 2012–2019 |
| Fluoride | 1086 µg/L 27% of the EPA limit 4000 µg/L
worst single sample: 1320 µg/L | 23/23 | SYR4 | 2012–2018 |
| Lead | 0.0027 mg/L 18% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Dichloroacetic Acid | 13.07 µg/L No EPA limit set
worst single sample: 14.4 µg/L | 15/28 | SYR4 | 2012–2019 |
| Bromoform | 1.935 µg/L No EPA limit set
worst single sample: 2.037 µg/L | 13/28 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.0415 pCi/L 61% of the EPA limit 5 pCi/L
worst single sample: 3.19 pCi/L | 12/19 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 3.17 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 12/28 | SYR4 | 2012–2019 |
| Lithium | 10.8 µg/L No EPA limit set | 4/16 | UCMR-5 | 2025 |
| Arsenic | 1.56 µg/L 16% of the EPA limit 10 µg/L
worst single sample: 1.6 µg/L | 3/23 | SYR4 | 2012–2018 |
| Lead | 4.19 µg/L 28% of the EPA limit 15 µg/L
worst single sample: 4.2 µg/L | 3/60 | SYR4 | 2014–2017 |
| Cadmium | 1 µg/L 20% of the EPA limit 5 µg/L | 1/23 | SYR4 | 2012–2018 |
| Chromium | 5.2 µg/L 5.2% of the EPA limit 100 µg/L | 1/23 | SYR4 | 2012–2018 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Lake in the Hills
Is Lake in the Hills tap water safe to drink?
EPA monitoring detected 19 contaminants in Lake in the Hills's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lake in the Hills's water?
EPA monitoring detected Copper, Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Lake in the Hills serve?
Lake in the Hills reports serving 28,661 people in Illinois, per its EPA record.
Has Lake in the Hills had any water quality violations?
The EPA has 44 violations on file for Lake in the Hills, of which 18 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.