Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
| TT | Health-based | Resolved | 1993-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1196.5 µg/L 92% of the EPA limit 1300 µg/L
worst single sample: 2260 µg/L | 90/90 | SYR4 | 2013–2019 |
| Lead | 15.1 µg/L 101% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 31.8 µg/L | 41/92 | SYR4 | 2013–2019 |
| Lead | 0.0105 mg/L 70% of the EPA limit 0.0150 mg/L | 34/34 | LCR | 2025 |
| Bromoform | 19.88 µg/L No EPA limit set
worst single sample: 28.8 µg/L | 32/32 | SYR4 | 2012–2019 |
| TTHM | 20.76 µg/L 26% of the EPA limit 80 µg/L
worst single sample: 29.5 µg/L | 32/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 3.8705 µg/L 6.5% of the EPA limit 60 µg/L
worst single sample: 4.71 µg/L | 30/32 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.3785 µg/L No EPA limit set
worst single sample: 3.59 µg/L | 24/32 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.855 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 15/32 | SYR4 | 2012–2019 |
| Nitrate | 365 µg/L 3.7% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 5.525 pCi/L 111% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.2 pCi/L | 10/10 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 3.92 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 7/32 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 336.25 µg/L 3.4% of the EPA limit 10000 µg/L
worst single sample: 365 µg/L | 6/6 | SYR4 | 2012–2019 |
| Barium | 13.08 µg/L 0.7% of the EPA limit 2000 µg/L
worst single sample: 13.2 µg/L | 2/2 | SYR4 | 2014–2017 |
| Fluoride | 1026.3 µg/L 26% of the EPA limit 4000 µg/L
worst single sample: 1030 µg/L | 2/2 | SYR4 | 2014–2017 |
| Lithium | 75.7 µg/L No EPA limit set | 2/2 | UCMR-5 | 2023 |
| Nitrite | 10 µg/L 1% of the EPA limit 1000 µg/L | 1/7 | SYR4 | 2012–2019 |
| Thallium, Total | 2.6 µg/L 130% of the EPA limit, at the 95th percentile of samples — 2 µg/L | 1/3 | SYR4 | 2014–2017 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Peru
Is Peru tap water safe to drink?
EPA monitoring detected 17 contaminants in Peru's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Peru's water?
EPA monitoring detected Copper, Lead, Lead, Bromoform, TTHM, and others. The full list with the level and data source for each is above.
How many people does Peru serve?
Peru reports serving 10,300 people in Illinois, per its EPA record.
Has Peru had any water quality violations?
The EPA has 29 violations on file for Peru, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.