← Illinois

Tap water quality report

Herscher

EPA monitoring tested this supplier for 80 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
16
detected
1,600
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Kankakee

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
8
violations on file
2
still open
ViolationTypeStatusPeriod
RPT Monitoring Unaddressed 2025-07-02
RPT Monitoring Unaddressed 2025-07-02
MR Monitoring Archived 2002-05-01 → 2002-05-31
MR Monitoring Archived 2002-05-01 → 2002-05-31
MR Monitoring Archived 1995-04-01 → 1995-04-30
MR Monitoring Archived 1995-04-01 → 1995-04-30
MR Monitoring Archived 1995-04-01 → 1995-04-30
MR Monitoring Archived 1977-06-30 → 1981-06-29

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
290 µg/L 22%
of the EPA limit 1300 µg/L
worst single sample: 458 µg/L
17/30 SYR4 2012–2018
Lead
0.0106 mg/L 71%
of the EPA limit 0.0150 mg/L
16/16 LCR 2025
Chloroform
4.86 µg/L
No EPA limit set
worst single sample: 6.4 µg/L
8/8 SYR4 2012–2019
Dichloroacetic Acid
2.365 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
8/8 SYR4 2012–2019
TTHM
8.045 µg/L 10%
of the EPA limit 80 µg/L
worst single sample: 11.3 µg/L
8/8 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
3.32 µg/L 5.5%
of the EPA limit 60 µg/L
worst single sample: 3.6 µg/L
8/8 SYR4 2012–2019
Fluoride
497.4 µg/L 12%
of the EPA limit 4000 µg/L
worst single sample: 519 µg/L
4/4 SYR4 2012–2018
Combined Radium (-226 And -228)
2.277 pCi/L 46%
of the EPA limit 5 pCi/L
worst single sample: 2.38 pCi/L
3/3 SYR4 2014–2017
Nitrate
160 µg/L 1.6%
of the EPA limit 10000 µg/L
2/24 SYR4 2012–2019
Trichloroacetic Acid
1.585 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
2/8 SYR4 2012–2019
Arsenic
0.7280 µg/L 7.3%
of the EPA limit 10 µg/L
1/4 SYR4 2012–2018
Barium
16.5 µg/L 0.8%
of the EPA limit 2000 µg/L
1/4 SYR4 2012–2018
Bromodichloromethane
3.4 µg/L
No EPA limit set
1/8 SYR4 2012–2019
Dibromochloromethane
1.5 µg/L
No EPA limit set
1/8 SYR4 2012–2019
Lead
23 µg/L 153%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
1/30 SYR4 2012–2018
Nitrate-Nitrite
160 µg/L 1.6%
of the EPA limit 10000 µg/L
1/12 SYR4 2012–2019
64 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BAUER, JEREMY
Phone
815-426-2131
Email
[email protected]

Frequently asked questions about Herscher

Is Herscher tap water safe to drink?

EPA monitoring detected 16 contaminants in Herscher's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Herscher's water?

EPA monitoring detected Copper, Lead, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.

How many people does Herscher serve?

Herscher reports serving 1,600 people in Illinois, per its EPA record.

Has Herscher had any water quality violations?

The EPA has 8 violations on file for Herscher, of which 0 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.