Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2015-12-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-12-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-12-01 → 2015-12-31 |
| MCL | Health-based | Resolved | 2015-12-01 → 2015-12-31 |
| MCL | Health-based | Archived | 1998-07-01 → 1998-07-31 |
| MCL | Health-based | Archived | 1998-07-01 → 1998-07-31 |
| Other | Monitoring | Resolved | 2026-01-17 |
| Other | Monitoring | Resolved | 2026-01-17 |
| Other | Monitoring | Resolved | 2026-01-17 |
| Other | Monitoring | Resolved | 2026-01-17 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0062 µg/L | 1/16 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 458 µg/L 35% of the EPA limit 1300 µg/L
worst single sample: 810 µg/L | 285/293 | SYR4 | 2012–2019 |
| Chlorite | 960 µg/L 96% of the EPA limit 1000 µg/L
worst single sample: 1100 µg/L | 141/151 | SYR4 | 2012–2019 |
| Lead | 16.2 µg/L 108% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 36 µg/L | 129/293 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.635 µg/L No EPA limit set
worst single sample: 9.74 µg/L | 116/116 | SYR4 | 2012–2019 |
| Chloroform | 19.675 µg/L No EPA limit set
worst single sample: 57.4 µg/L | 116/116 | SYR4 | 2012–2019 |
| TTHM | 29.475 µg/L 37% of the EPA limit 80 µg/L
worst single sample: 67 µg/L | 116/116 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.9655 µg/L No EPA limit set
worst single sample: 6.72 µg/L | 110/116 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 22.28 µg/L 37% of the EPA limit 60 µg/L
worst single sample: 37.4 µg/L | 102/116 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 16.08 µg/L No EPA limit set
worst single sample: 23.7 µg/L | 97/116 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.4305 µg/L No EPA limit set
worst single sample: 13.7 µg/L | 80/116 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 57/57 | LCR | 2026 |
| Nitrate | 1755 µg/L 18% of the EPA limit 10000 µg/L
worst single sample: 1800 µg/L | 30/44 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.161 µg/L No EPA limit set
worst single sample: 2.18 µg/L | 27/116 | SYR4 | 2012–2019 |
| Bromoform | 1.786 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 22/116 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 12.465 µg/L No EPA limit set
worst single sample: 18.2 µg/L | 22/116 | SYR4 | 2012–2019 |
| Barium | 320 µg/L 16% of the EPA limit 2000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.312 pCi/L 26% of the EPA limit 5 pCi/L
worst single sample: 1.4 pCi/L | 12/12 | SYR4 | 2012–2015 |
| Fluoride | 964.95 µg/L 24% of the EPA limit 4000 µg/L
worst single sample: 978 µg/L | 10/16 | SYR4 | 2012–2019 |
| Arsenic | 1.275 µg/L 13% of the EPA limit 10 µg/L
worst single sample: 1.3 µg/L | 6/16 | SYR4 | 2012–2019 |
| Atrazine | 0.5800 µg/L 19% of the EPA limit 3 µg/L
worst single sample: 0.5900 µg/L | 5/33 | SYR4 | 2012–2019 |
| Simazine | 1 µg/L 25% of the EPA limit 4 µg/L
worst single sample: 1.1 µg/L | 5/32 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1790 µg/L 18% of the EPA limit 10000 µg/L
worst single sample: 1800 µg/L | 3/9 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 4.347 µg/L No EPA limit set
worst single sample: 4.46 µg/L | 2/116 | SYR4 | 2012–2019 |
| Selenium | 2.6 µg/L 5.2% of the EPA limit 50 µg/L | 1/16 | SYR4 | 2012–2019 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Ej Water Cooperative
Is Ej Water Cooperative tap water safe to drink?
EPA monitoring detected 25 contaminants in Ej Water Cooperative's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ej Water Cooperative's water?
EPA monitoring detected Copper, Chlorite, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Ej Water Cooperative serve?
Ej Water Cooperative reports serving 29,720 people in Illinois, per its EPA record.
Has Ej Water Cooperative had any water quality violations?
The EPA has 107 violations on file for Ej Water Cooperative, of which 6 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.